Detailed Description of the Parameters
.
CTW900 | 65
P0213 – Full Scale Reading Parameter 1
P0214 – Full Scale Reading Parameter 2
P0215 – Full Scale Reading Parameter 3
Adjustable Range:
0 to 200.0 %
Factory Setting:
100.0 %
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
20 HMI
Description:
These parameters configure the full scale of the reading variables 1, 2 and 3 (selected through P0205, P0206
and P0207), when they are programmed to be presented as bar graphs.
P0216 – HMI Display Contrast
Adjustable Range:
0 to 37
Factory Setting:
27
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
20 HMI
Description:
It allows setting the keypad (HMI) display contrast level. Higher values configure a higher contrast level.
7.3.2
Ramps [21]
The inverter Ramp functions allow the motor to accelerate or decelerate faster or slower, or also according to a
specific profile.
P0100 – Acceleration Time
P0101 – Deceleration Time
Adjustable Range:
0 to 999.0 s
Factory Setting:
20.0 s
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
21 Ramps
Description:
These parameters define the time to accelerate (P0100) linearly from zero to the maximum speed (defined in
P0134) and decelerate (P0101) linearly from the maximum speed to zero.
Note:
The setting in 0.0s means the ramp is disabled.
P0102 – Acceleration Time of the 2nd Ramp
P0103 – Deceleration Time of the 2nd Ramp
Adjustable Range:
0 to 999.0 s
Factory Setting:
20.0 s
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
21 Ramps
Description:
These parameters allow configuring a second motor acceleration (P0102) or deceleration (P0103) ramp, which
is activated via external digital command (defined by P0105). Once this command is activated, the converter
ignores the time of the first ramp (P0100 or P0101) and follows the value set for the second ramp (see example
for external command via Dix in Figure 7.1 below).
Содержание CTW900
Страница 2: ......
Страница 52: ...Installation and Connection 52 CTW900 Figure 5 16 Connections in XC1 for configuration 4...
Страница 69: ...Detailed Description of the Parameters CTW900 69 Figure 7 3 Block diagram of the speed reference...
Страница 135: ...Detailed Description of the Parameters CTW900 135 Figure 7 21 Block diagram of the control of the CTW900...