Start-up
.
56 | CTW900
6.2.3
Setting the Parameters of the Basic Application
After executing the Oriented Start-up routine and the proper setting of its parameters, the converter will be
ready to operate with the configured line and motor.
However, the CTW900 has a series of other parameters that allow its adaptation to a variety of applications.
This section presents some basic parameters whose setting is necessary in most cases. In order to set them,
you can use the Basic Application parameter group, as shown in Figure 6.3.
More details on each parameter available on the CTW900 can be seen in Chapter 7 of this manual.
Seq.
Action/Result
Indication on the display
Seq.
Action/Result
Indication on the display
1
- Monitoring Mode
- Press
“Menu”
(left
soft key).
5
- Proceed in a similar
way until setting all the
parameters contained in
the Basic Application
group.
2
- The group “
00 ALL
PARAMETERS
” is
selected.
- Press
“
”
until
selecting the group
“04 BASIC
APPLICATION”
.
6
- Press “
Return
”.
3
- The group
“04
BASIC
APPLICATION”
is
selected then.
- Press
“Select”
.
7
- The display returns to
the Monitoring Mode
and the converter is
ready to operate.
4
- The parameter
“Acceleration
Time”
(P0100) is
already selected.
- If necessary, set
P0100 and P0101 to
another value,
according to the
desired time. In order
to do so, press
“Select”,“
”
or
“
”
and then
“Save”
.
Figure 6.3
– Setting the parameters of the Basic Application group
6.2.4
Disabling the Parameter Modification
In case you want to prevent non-authorized people from changing parameters, just change the content of
P0000 to a value different from 5.
Follow basically the same procedure presented in item 6.2.1.
6.3
SETTING THE SPEED FEEDBACK
Depending on the motor or sensor used for the speed feedback, some parameter setting may be necessary for
the motor speed displayed on the keypad to have the smallest possible error.
Therefore, follow one of the procedures below according to the type of speed feedback used.