![Weq CTW900 Скачать руководство пользователя страница 122](http://html1.mh-extra.com/html/weq/ctw900/ctw900_user-manual_957086122.webp)
Detailed Description of the Parameters
.
122 | CTW900
The operation of loading one of those memories can also be done via digital inputs (DIx). For further details on
programming, refer to the item 7.3.14.
NOTE!
When P0204 = 3, parameters P0201 (Language), P0296 (Line Rated Voltage) and P0308 (Serial
Address) are not changed to the factory settings.
P0318 – Copy Function of Memory Card
Adjustable Range:
0 = Inactive
Factory Setting:
0
1 = CTW900
Memory Card
2 = Memory Card
CTW900
Properties:
CFG1
Groups of Acess via HMI:
06 BACKUP PARAMETERS
...
Description:
This function allows saving the content of the writing parameters of the CTW900 to the FLASH Memory Module
(MMF), and vice-versa, and can be used to transfer the content of the parameters from one CTW900 to
another.
Table 7.24
– Options of parameter P0318
P0318
Action
0
Inactive
:
no action.
1
CTW900
Memory Card
:
transfers the present content of the CTW900 parameters to the Flash
memory.
2
Memory Card
CTW900
:
transfers the content of the parameters stored in the Flash memory to
the control board of the CTW900.
After storing the parameters of the CTW900 in a FLASH Memory Module, it is possible to transfer them to
another CTW900 using this function. However, if the converters have incompatible software versions, the
keypad will display the message: “FLASH Memory Module with invalid parameters” and the copy will not be
done.
Note:
This parameter will only be visible if the FLASH memory module is installed on the converter.
NOTE!
During the operation of the CTW900, the modified parameters are saved on the FLASH Memory
Module, regardless of the user’s command. This ensures that the flash memory module will always
have an updated copy of the converter parameters.
NOTE!
When the CTW900 is powered and the memory module is present, the present parameter
contents are compared to the contents of the parameters saved on the flash memory module and,
in case they are different, the keypad (HMI) will display the message “FLASH Memory Module with
different parameters” and, after 3 seconds, the message is replaced by P0318 parameter menu.
The user has the option of overwriting the contents of the memory module (choosing P0318 = 1) or
overwriting the converter parameters (choosing P0318 = 2), or even ignoring the message by
choosing P0318 = 0.
NOTE!
When using the network communication board or SoftPLC function, it is recommended to set the
parameter P0318 = 0.