Detailed Description of the Parameters
.
134 | CTW900
7.11
PARAMETER INCOMPATIBILITY
In order to prevent drive or control problems, the CTW900 identifies and signals parameterization combinations
that can lead to an undefined operating situation.
Thus, in case some of the conditions of Table 7.27 occurs, the converter will signal the incompatibility on the
display and will go into the Configuration status (“Config”, on the keypad), preventing its enabling until the
programming conflict is solved.
Table 7.27
– Parameter incompatibility
Incompatible Programming
Related Parameter
Group
Parameters to Be Checked
Multiple AIs programmed for “Pos. Curr. Lim.” (option 3) or “I+/I- Curr.
Lim.” (option 5).
[32] Analog Inputs
P0231, P0236, P0241, P0246
Multiple AIs programmed for “Neg. Curr. Lim.” (option 4) or “I+/I- Curr.
Lim.“ (option 5).
Multiple DIs programmed for “Forward Run” function (option 4).
[34] Digital Inputs
P0263, P0264, P0265, P0266
P0267, P0268, P0269, P0270
Multiple DIs programmed for “Reverse Run” function (option 5).
Multiple DIs programmed for “3-Wire Start” function (option 6).
Multiple DIs programmed for “3-Wire Stop” function (option 7).
Multiple DIs programmed for “FWD/REV” function (option 8).
Multiple DIs programmed for “Local/Remote” function (option 9).
Multiple DIs programmed for “Increase E.P.” function (option 11).
Multiple DIs programmed for “Decrease E.P.” function
(option 12).
Multiple DIs programmed for “2nd Ramp” function (option 14).
Multiple DIs programmed for “Speed/Torque” function (option 15).
Multiple DIs programmed for “Speed Regulator Gains” function (option
21).
Multiple DIs programmed for “Param. Setting Off” function (option 22).
Multiple DIs programmed for “Load User 1/2” function (option 23).
Multiple DIs programmed for “Load User 3” function (option 24).
DIx programmed for the “Forward Run” function without DIx
programmed for the “Reverse Run” function.
DIx programmed for the “Reverse Run” function without DIx programmed
for the “Forward Run” function.
DIx programmed for the “Start” function without DIx programmed for the
“Stop” function.
DIx programmed for the “Stop” function without DIx programmed for the
“Start” function.
DIx programmed for the “Run/Stop” (option 1) +
DIx programmed for the “3-Wire Start” function.
DIx programmed for the “Run/Stop” (option 1) +
DIx programmed for the “Forward Run” function.
DIx programmed for the “FWD/REV” function (option 8) +
DIx programmed for the “Reverse Run” function.
DIx programmed for the “Increase E.P.” function without DIx
programmed for the “Decrease E.P.”.
DIx programmed for the “Decrease E.P.” function without DIx
programmed for the “Increase E.P.”.
P0221 and/or P0222 = E.P. (option 7) without DIx programmed for
“Increase E.P.” or “Decrease E.P.”.
P0224 and/or P0227 = DIx (option 1) without DIx programmed for
“Run/Stop”.
P0223 and/or P0226 = DIx (option 1) without DIx programmed for
“FWD/REV” or “Reverse Run”.
P0221 and/or P0222 = Multispeed (option 8) without DIx programmed
for “Multispeed” (option 13).
[34] Digital Inputs
P0266, P0267, P0268
DIx programmed for “Increase E.P.” or “Decrease E.P.” without P0221
and/or P0222 programmed for “E.P.”.
[27] Local Control
[28] Remote Control
[29] Run/JOG Config.
P0221, P0222, P0223,
P0224, P0226, P0227
DIx programmed for “Multispeed” without P0221 and/or P0222
programmed for “Multispeed”.
DIx programmed for the “Forward Run” function without P0224 or P0227
programmed for “DIx”.
DIx programmed for the “Reverse Run” function without P0223 or P0226
programmed for “DIx”.
Содержание CTW900
Страница 2: ......
Страница 52: ...Installation and Connection 52 CTW900 Figure 5 16 Connections in XC1 for configuration 4...
Страница 69: ...Detailed Description of the Parameters CTW900 69 Figure 7 3 Block diagram of the speed reference...
Страница 135: ...Detailed Description of the Parameters CTW900 135 Figure 7 21 Block diagram of the control of the CTW900...