Detailed Description of the Parameters
.
CTW900 | 131
P0022 – Tacho DC Voltage
Adjustable Range:
-500.0 to 500.0 V
Factory Setting:
Properties:
RO
Groups of
09 READ ONLY PARAMETERS
Access via HMI:
Description:
It indicates the present voltage of the motor DC tacho, in Volts (V).
P0023 – Software Version
Refer to section 7.3.16.
P0024 – Armature Firing Angle
P0025 – Field Firing Angle
Adjustable Range:
0.0 to 180.0 °
Factory Setting:
Properties:
RO
Groups of
09 READ ONLY PARAMETERS
Access via HMI:
Description:
It indicates the present firing angle of the armature bridges (P0024) and of the field (P0025) in electric degrees.
P0026 – EMF Voltage
Adjustable Range:
-2000 to 2000 V
Factory Setting:
Properties:
RO
Groups of
09 READ ONLY PARAMETERS
Access via HMI:
Description:
It indicates the present EMF voltage of the motor in Volts (V).
This parameter will only have value different from P0007 when the value of the armature resistance (P0409) is
not null.
P0027 – Configuration of Accessories 1
P0028 – Configuration of Accessories 2
Refer to the section 7.3.16.
P0030 – Heatsink Temperature
Refer to the section 7.3.18.
P0033 – Line Voltage R-S
P0034 – Line Voltage S-T
P0035 – Line Voltage T-R
Adjustable Range:
0 to 1000 V
Factory Setting:
Properties:
RO
Groups of
09 READ ONLY PARAMETERS
Access via HMI:
Description:
They indicate the voltages of the power line (R/S/T) in Volts (V).
P0038 – Encoder Speed
Adjustable Range:
0 to 65535 rpm
Factory Setting:
Properties:
RO
Groups of
09 READ ONLY PARAMETERS
Access via HMI: