Faults and Alarms
.
24 | CTW900
Fault/Alarm
Description
Possible Causes
F003:
Line Undervoltage
■
Actuates when the line voltage remains below the value
defined in P0362 (in percentage of P0296) for a period longer
than the time set in P0357.
( ) =
(100%
−
0362)
×
0296
■
Setting of P0296 in a range above the
rated line voltage.
■
Input fuses open.
■
Loss of a line phase.
F004:
Line Overvoltage
■
Actuates when the line voltage remains above the value
defined in P0361 (in percentage of P0296) for over 5 seconds.
( ) = (100
% + 0361)
×
0296
■
Power supply above the maximum value.
■
Setting of P0296 in a range below the
rated line voltage.
F006:
Unbalance of the Line
Voltages
■
Actuates when the difference between the line voltage values
(P0033, P0034 and P0035) remain above the value set in P0363
for over 2 seconds (value of P0363 in percentage of P0296).
(%) =
| 0033
−
0034|
0296
×
100
%
(%) =
| 0034
−
0035|
0296
×
100
%
(%) =
| 0033
−
0035|
0296
×
100
%
■
The line voltage unbalance is above the
setting.
■
System unbalanced.
■
One of the input fuses open.
■
Loss of a line phase.
F008:
Line Under/Over
Frequency
■
Actuates when the line frequency is above or below the
maximum variation set in P0364 (in percentage of the rated
frequency).
.
. (
) = (100
% + 0364) ×
(50
/
60
)
.
. (
) = (100
%
−
0364) ×
(50
/
60
)
■
Line frequency above or below the
maximum acceptable variation.
■
One of the input fuses open.
■
Loss of a line phase.
F009:
Field Supply Under/Over
Frequency
■
Actuates when the field supply frequency is above or below
the maximum variation set in P0364 (in percentage of the rated
frequency).
.
. (
) = (100
% + 0364) ×
(50
/
60
)
.
. (
) = (100
%
−
0364) ×
(50
/
60
)
Note: Relevant fault only when the field is supplied externally by
means of connector X3. Otherwise, the field frequency will be the
same as the converter main supply (R/S/T).
■
Field supply frequency above or below
the maximum acceptable variation.
■
One of the field supply fuses open.
F022:
Armature Overvoltage
■
Actuates when the armature voltage exceeds the maximum
level defined by P0358 (in percentage of P0400) for over 2
seconds.
( ) = (100
% + 0358)
×
0400
■
Motor is being accelerated by the load.
■
Incorrect value set in P0400.
■
Overvoltage level set too low (P0358).
■
Incorrect field current setting (P0404 and
P0177).
■
Incorrect speed feedback configuration
(tacho / encoder).
A046:
High Load on the Motor
■
Signals when the armature current (P0003) is above the
overload level defined by P0349 (in percentage of P0156).
( ) = 0349
×
0156
Note: This alarm will be active if the following conditions are met:
■
P0156 > P0157 and
■
P0348 = 1 or P0348 = 3.
■
High load on the motor shaft.
■
Rotor locked.
■
Overload level set too low (P0156).
A050:
High Temperature on
Heatsink
■
Signals when the temperature measured on the heatsink is
above 85°C.
Note: The alarm will be removed when the temperature fall
below 82°C.
■
Load requiring a constant current close
to the converter rated capacity.
■
Fault on the fans of product.
■
Improper installation with obstruction of
the inlets and/or outlets of the product.
F051:
Converter
Overtemperature
■
Actuates when the temperature measured on the heatsink
reaches 90°C.
Note: Fault can only be reset when the temperature is below
82°C.
■
Load cycle incompatible with the
converter rated current.
■
Ambient temperature above the
maximum acceptable (40°C).
■
Fault on the fans of product.
■
Improper installation with obstruction of
the inlets and/or outlets of the product.