Detailed Description of the Parameters
.
CTW900 | 127
P0094 – Field Current at the Moment of the Last Fault
Adjustable Range:
0 to 60.0 A
Factory Setting:
Properties:
RO
Groups of
08 FAULT HISTORY
Access via HMI:
Description:
Record of the field current supplied by the converter at the moment of the occurrence of the last fault.
P0096 – DIx Status at the Moment of the Last Fault
Adjustable Range:
Bit 0 = DI1
Factory Setting:
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
Properties:
RO
Groups of
08 FAULT HISTORY
Access via HMI:
Description:
It indicates the status of the digital inputs at the moment of the last fault occurrence.
The indication is done by means of the numbers 1 and 0, representing, respectively, the “Active” and “Inactive”
status of the inputs. The status of each input is considered as one digit in the sequence, where DI1 represents
the least significant digit.
Example: If parameter P0096 contains the sequence
00010011
, it means digital inputs 5, 2 and 1 were active at
the moment of occurrence of the last fault.
P0097 – DOx Status at the Moment of the Last Fault
Adjustable Range:
Bit 0 = DO1
Factory Setting:
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Properties:
RO
Groups of
08 FAULT HISTORY
Access via HMI:
Description:
It indicates the status of the digital outputs at the moment of the occurrence of the last fault.
The indication is done by means of the numbers 1 and 0, representing, respectively, the “Active” and “Inactive”
status of the outputs. The status of each output is considered as one digit in the sequence, where DO1
represents the least significant digit.
Example: If parameter P0097 contains the sequence
01001
, it means digital outputs 4 and 1 were active at the
moment of occurrence of the last fault.
7.10
READ ONLY PARAMETERS [09]
In order to simplify the view of the main reading variables of the do CTW900, you may directly access the group
[09] – “Read Only Parameters”.
It is important to point out that all the parameters of this group can only be viewed on the keypad display, and
cannot be changed by the user.