Flow-X─ Function Reference
Flow-X General functions - fxAPI_SG60F_1952
Conversion
method
1: From observed to standard
conditions
2: From standard to observed
conditions
CONVERSIO
N
1
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
3: No convergence
-
STS
FIOOR
CALCERR
NOCONV
1
Output Specific
Gravity
Depending on the conversion
method this is the Specific Gravity
either at 60
°
F and the equilibrium
pressure or at the observed
temperature and observed
pressure
-
RD
0
CTL
Volume correction factor for
temperature.
-
CTL
1
CPL
Volume correction factor for
pressure
Value will be rounded according to
input 'API 11.2.1 rounding'
-
CPL
1
CTPL
Combined volume correction
factor
CTPL = CTL * CPL
-
CTPL
1
F
Compressibility factor
-
F
0
CTL calc out of
range
With respect to the standard used
for the calculation of CTL the
combination of input values is:
0: In Range
1: Out of Range
CTLOOR
0
CPL calc out of
range
With respect to the standard used
for the calculation of CPL the
combination of input values is:
0: In Range
1: Out of Range
CPLOOR
0
Calculations
The calculations depend on the conversion method.
Conversion method 1: from observed to standard conditions.
The function performs the following iterative algorithm to calculate the Specific Gravity at standard
conditions:
1.
At the start of the iteration the initial value for Specific Gravity at [60
F,
equilibrium pressure] is set to the Observed Specific Gravity. The initial CPL value
is set to 1.
2.
The CTL value is determined from the Specific Gravity at [60
F, equilibrium
pressure] according to API 1952 Table 24.
3.
The Specific Gravity at [60
F, equilibrium pressure] is calculated from the
Observed specific gravity, the new CTL value and the CPL value from the previous
iteration.
4.
Because API 11.2.1 requires the API gravity value at 60
F, the API gravity at [60
F, equilibrium pressure] is calculated from the Specific gravity at [60
F,
equilibrium pressure].
5.
The compressibility factor is calculated according to API MPMS 11.2.1 from the
API gravity at [60
F, equilibrium pressure] and the 'Observed temperature'. If API
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...