Flow-X─ Function Reference
Flow-X IO Functions - fxPulseOutput
fxPulseOutput
This function is used to feed pulses to an electro-mechanical (E/M) counter. There are 4 pulse output
units, to be selected by the index parameter. The function uses a reservoir to accumulate the pulses.
On one hand the number of pulses that need to be added to the reservoir is calculated from inputs
'Increment' and ‘Significance factor'. On the other hand pulses are taken from the reservoir and fed to
the E/M counter at a rate that will not exceed the specified output rate.
This can also be used to configure a dual pulse situation, for this case you can configure a second
channel and the delay it has on the primary channel.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag description
and tag group
Index
Index number 1..4.
INDEX
1..4
1
Channel
Digital I/O channel number
0 disables the function
CHAN
0..16
0
Significance factor
Factor that specifies the relation
between the Increment value and
the number of output pulses.
E.g. a value of 100 means that 1
pulse is generated whenever 100
increment units have been
accumulated.
-
SIGFCT
0..1e99
1
Pulse width
Time that each output pulse
remains active (high) in millisecond
Restriction (pulse duty cycle is 50%):
Pulse width <= 1000 / (2* max.
output rate)
ms
PLSWID
0..1e6
20
Max. output rate
Maximum pulse output rate.
When output pulses are generated
at a frequency higher than the
maximum output rate, the
superfluous pulses will be
accumulated in the pulse reservoir.
Restriction when pulse duty cycle
should not exceed 50%:
Max. output rate <= 1000 / (2*
Pulse width)
Hz
MAXFREQ
0..1e6
40
Reservoir alarm
limit
Alarm limit for the number of
pulses in the reservoir buffer
-
RSVLIM
0..1e99
1e9
Channel 2
Digital I/O channel number
0 disables the function
CHAN
0..16
0
Delay
Delay between dual pulse channel
A and B in milliseconds
ms
0..1e99
0
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range or in
conflict
-
STS
FIOOR
Pulse reservoir
Number of pulses that are
accumulated in the reservoir.
-
RSVPLS
0
Reservoir alarm
status
With respect to the 'Reservoir alarm
limit' the number of pulses in the
reservoir is:
0: Within limit
1: Out of limit
-
RSVSTS
RSVALM
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...