5-316
Flow-X─ Function Reference
Flow-X IO Functions - fxAnalogOutput
fxAnalogOutput
This function configures a single 4-20 mA output channel on the local Flow-X module. Use function
'fxSetAnalogOutput' to control the actual output signal.
The output current is either set directly or gradually changed to the required set point based on the
specified filter method.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional Optional tag name, tag
description and tag group
<Empty>
Channel
number
1..4
CHAN
0
Filter setpoint
0 .. 15
0: No filtering
1: Fastest filter
..
15: Slowest filter
FILSP
0
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Function Input argument out of range
STS
FIOOR
Percentage value
The actual (and filtered) output value
expressed as a percentage
%
PERC
0
fxSetAnalogOutput
This function writes an analog value to an output. Make sure that the analog output has been set up by
calling fxAnalogOutput first.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional Optional tag name, tag
description and tag group
<Empty>
Module
Not used, set to -1
-1..16
-1
Channel
number
1..4
CHAN
0
Filter setpoint
0 .. 15
0: No filtering
1: Fastest filter
..
15: Slowest filter
FILSP
0
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Function Input argument out of range
STS
FIOOR
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...