Flow-X─ Function Reference
4-269
Flow-X General functions - fxROCAlarm
fxROCAlarm
Description
The function checks if a value does not change its value at a rate that is higher than a specific limit
(‘rate of change’).
Function inputs and outputs
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name,
tag description and
tag group
Input value
Must be linked to
another cell
Same as linked
cell
-1e11..1e11
0
Rate of change
limit
The unit depends
on the 'Deviation
type'
Absolute: Same as
input value 1 / s
Relative : % /s
ROCLIM
0..1e11
0
Enabled
Enables or disabled
the alarm
True or false
True
Alarm type
1: Alarm
2: Warning
1
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Rate of change alarm
0: Normal
1: Alarm
-
ROCALM
ROCALM
Logic
A 'Rate of change alarm' is raised when the absolute difference between two consecutive values divided
by the calculation cycle time in seconds is more than the limit.
fxSarasota_C
The function calculates the density from a frequency input signal provided by a Sarasota densitometer
and corrects it for temperature and pressure effects in US customary units.
Note: The calibration constants also need to be in US customary units (°F, psi and lbm/ft3).
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag
description and tag
group
Periodic time
In microseconds
Equals 1000 divided by
the frequency in [Hz]
s
0..1e6
0
Line temperature
Used when temperature
correction is enabled
°F
-
273.15..+500
20
Line pressure
Used when pressure
correction is enabled
psig
0..200
0
Temperature
correction
0: Disabled
1: Enabled
-
TEMPCOR
1
Pressure correction
0: Disabled
1: Enabled
-
PRESCOR
1
Reference
temperature
Used when temperature
correction is enabled
°F
REFTEMP
0..100
20
Reference pressure
Used when pressure
psig
REFPRES
0..100
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...