Flow-X─ Function Reference
Flow-X General functions - fxAPI_RD60F_NGL_LPG
and the equilibrium pressure or
at the observed temperature and
pressure
density
CTL
Volume correction factor for
temperature.
Value will be rounded according
to input 'API 11.2.4 rounding'
-
CTL
1
CPL
Volume correction factor for
pressure
Value will be rounded according
to input 'API 11.2.2. rounding'
-
CPL
1
CTPL
Combined volume correction
factor
CTPL = CTL * CPL
-
CTPL
1
F
Compressibility factor
The output value will be either
rounded or not depending input
'API rounding'
1/psi
F
0
Equilibrium
pressure
The equilibrium pressure
calculated by GPA TP-15
Will be set to 0 when equilibrium
pressure is below atmospheric
pressure
psia
EQUIPC
UR
0
CTL calc out of
range
With respect to the API 11.2.4
standard the combination of
input values is:
0: In Range
1: Out of Range
The following range checks
apply:
0.21 <= RD <= 0.74
-50.8 <= T <= 199.4 °F
Table 23E reference
fluid ranges
CTLOOR
0
CPL calc out of
range
With respect to API 11.2.2M the
combination of input values is:
0: In Range
1: Out of Range
The following range checks
apply:
350 <= Density 15 °C <=
637 kg/m3
-46 °C <= T <= 60 °C
Also the check on the pseudo-
critical temperature as defined
for fxAPI_MPMS_11_2_2 is
applied.
CPLOOR
0
GPA TP-15 out of
range
Only set when the GPA TP-15
calculation is enabled
With respect to the GPA TP-15
standard the combination of
input values is:
0: In Range
1: Out of Range
-
TP15OOR
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...