Flow-X─ Function Reference
Flow-X General functions - fxAGA3_C
Pressure
Location
1: Upstream tapping
Input 'Pressure' represents the
pressure at the upstream
pressure tapping (p
1
).
Since the absolute pressure is
usually measured at the
upstream tapping this is the
most common setting.
2: Downstream tapping
Input 'Pressure' represents the
pressure at the downstream
tapping (p
2
).
-
PRESL
OC
1
Temperature
Location
1: Upstream tapping
Input 'Temperature' represents
the upstream temperature (t
1
).
2: Downstream tapping
Input 'Temperature represents
the temperature at the
downstream tapping (t
2
).
3: Recovered pressure
Input 'Temperature' represents
the downstream temperature
at a location Where the
pressure has fully recovered
(t
3
).
Since temperature
measurement is usually
downstream of the flow device
this is the most common
setting.
-
TEMP
LOC
3
Temperature
Correction
1: Use (1-
)/
Isentropic expansion using (1-
)/
as the temperature
referral exponent
2: Use temperature exponent
Isentropic expansion using
input 'Temperature Exponent'
as the temperature referral
exponent [-]
-
TEMP
COR
1
Temperature
Exponent
To correct the temperature from
down- to upstream conditions (or
vice versa) the formula (
-1)/
(isentropic expansion) will be used
when the input value is set to 0,
else the input value will be used.
For more details refer to section
'Temperature correction'.
TEMP
EXP
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...