4-96
Flow-X─ Function Reference
Flow-X General functions - fxAPI_Gravity60F_1980
API-2540
rounding
0: Disabled
The calculations are performed
with full precision and the final
CTL value is rounded as
specified by input 'CTL decimal
places'
1: Enabled for computational value
API-2540 rounding and
truncating rules are applied
and, in case of conversion
method 2 (standard to
observed), the computational
value for CTL as specified in
Table 6 is used, meaning that
the CTL value has:
4 decimal places if CTL >=1
5 decimal places if CTL < 1.
2: Enabled for table value
API-2540 rounding and
truncating rules are applied
and, in case of conversion
method 2 (standard to
observed), the table value for
CTL as specified in Table 6
meaning that the CTL value has
4 decimal places in all cases
3: Enabled with 5 decimal places
API-2540 rounding and
truncating rules are applied,
and, in case of conversion
method 2 (standard to
observed), the CTL value has 5
decimal places in all cases.
Note: although not strictly in
accordance with the standard,
this option is more commonly
used than option 'Enabled for
computational value'
Note: for conversion type 1
‘From observed to standard
conditions’ the CTL factor is
rounded to 6 decimal places
when input ‘API 2540 rounding’
> 0, as in accordance with table
5.
API254
0RND
-
0
Hydrometer
correction
Only applies for conversion method
‘1: From observed to standard
conditions’
0: Disabled
1: Enabled
-
HYDRO
COR
0
API 11.2.1
rounding
0: Disabled
The calculation of the
compressibility factor F is
performed with full precision
1: Enabled
API-MPMS 11.2.1 rounding and
-
API112
1RND
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...