![Spirit flow-x Скачать руководство пользователя страница 302](http://html1.mh-extra.com/html/spirit/flow-x/flow-x_function-reference_1348386302.webp)
4-302
Flow-X─ Function Reference
Flow-X General functions - fxUGC_C
fxUGC_C
The function calculates the density from a frequency input signal provided by a UGC densitometer and
corrects it for temperature and pressure effects in US customary units.
Note: Calibration constants also need to be in US customary units.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag
description and tag group
Periodic time
In microseconds
Equals 1000 divided by the
frequency in [Hz]
s
0..1e6
Line temperature
Used when temperature
correction is enabled
°F
-
459.67..+1000
Line pressure
Used when pressure
correction is enabled
psig
0..3000
Temperature
correction
0: Disabled
1: Enabled
-
TEMPCOR
1
Pressure correction
0: Disabled
1: Enabled
-
PRESCOR
1
Reference
temperature
Used when temperature
correction is enabled
°F
REFTEMP
0..200
60
Reference pressure
Used when pressure
correction is enabled
psig
REFPRES
0..1500
0
K0
Constant K0 from calibration
certificate
-
K0
-1e9..1e9
K1
Constant K1 from calibration
certificate
-
K1
-1e9..1e9
K2
Constant K2 from calibration
certificate
-
K2
-1e9..1e9
KT1
Constant KT1 from
calibration certificate
KT1
-1e9..1e9
KT2
Constant KT2 from
calibration certificate
KT2
-1e9..1e9
KT3
Constant KT3 from
calibration certificate
KT3
-1e9..1e9
KP1
Constant KP1 from
calibration certificate
KP1
-1e9..1e9
KP2
Constant KP2 from
calibration certificate
KP2
-1e9..1e9
KP3
Constant KP3 from
calibration certificate
KP3
-1e9..1e9
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal (No error
condition)
1: Input argument out of
range
2: Calculation error
STS
FIOOR
CALC
Corrected density
Density corrected for
temperature and pressure
lbm/ft3
CORDENS
0
Uncorrected density
Uncorrected (indicated)
density
lbm/ft3
UNCDENS
0
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...