Flow-X─ Function Reference
4-163
Flow-X General functions -
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
3: No convergence
-
STS
FIOOR
CALCERR
Observed
density
Density at the observed
temperature and pressure
-
DENS
0
CTL
Volume correction factor for
temperature.
Value will be rounded according to
input 'API rounding'
-
CTL
1
CPL
Volume correction factor for
pressure
Value will be rounded according to
input 'API rounding'
-
CPL
1
CTPL
Combined volume correction factor
CTPL = CTL * CPL
-
CTPL
1
K0
Actual value of constant K0 used for
CTL calculation
-
K0
0
K1
Actual value of constant K1 used for
CTL calculation
-
K1
0
K2
Actual value of constant K2 used for
CTL calculation
-
K2
0
Alpha
Thermal expansion factor at 60
°
F !
1/°F
ALPHA
0
F
Compressibility factor
1/bar
F
0
Product
When input 'Product' is 'B - Auto
select', then the output is set to the
actual selected product of table B
(enumerative value as defined for
input 'Product'), else the output is
set equal to input 'Product'.
-
PRDCUR
0
Calculation
out of range
With respect to the standard the
input values are:
0: In Range
1: Out of Range
-
OOR
0
Calculations
The calculations are in either full or partial compliance with the standard, depending on whether API
rounding is enabled or not.
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...