Flow-X─ Function Reference
4-247
Flow-X General functions - fxLimitAlarm
fxLimitAlarm
Description
The function applies alarm limits on any value.
Function inputs and outputs
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name
Input value
Must be linked to
another cell
Same as
linked cell
INPVAL
-1e11..1e11
0
Low limit value
Same as
Input
value
LLIM
-1e11..1e11
-1e11
High limit value
Same as
Input
value
HLIM
Low limit value
.. 1e11
-1e11
Low low limit
value
Same as
Input
value
LLLIM
-1e11.. Low limit
value
1e11
High high limit
value
Same as
Input
value
HHLIM
High limit value
.. 1e11
1e11
Deadband
Same as
Input
value
0..1e11
0
Enabled
Enables or disables the
alarm
True or false
True
Warning
behavior
Determines the warning
behavior when the lo
and hi limit are violated:
1: No warnings, just
alarms
2: Warn on lo limit
3: Warn on hi limit
4: Warn on lo and hi limit
1
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Alarm status
0: Normal
1: Low alarm
2: High alarm
3: Low low alarm
4: High high alarm
-
ALMSTS
LALM
HALM
LLALM
HHALM
Logic
The order of priority in setting the alarm status output is as follows:
1.
If process value is below the ‘Low low limit value’ then the status becomes ‘3: Low low
alarm’.
2.
Else if process value is above the ‘High high limit value’ then the status becomes ‘4: High high
alarm’.
3.
Else if process value is below the ‘Low limit value’ then the status becomes ‘1: Low alarm’.
4.
Else if process value is above the ‘High limit value’ then the status becomes ‘2: High alarm’
and the ‘High high alarm’ is raised
5.
Else the status becomes ‘0: Normal’.
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...