Flow-X─ Function Reference
5-329
Flow-X IO Functions - fxSetPulseOutput
Calculations
Every calculation cycle a number of pulses is added to the reservoir that is equal to input value
'Increment' divided by input value Significance factor.
fxSetPulseOutput
Adds pulses to the reservoir, to be output on the next cycle. Takes the ‘significance factor’ into account,
see fxPulseOutput.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag description
and tag group
module
Not used, set to -1.
-1..16
-1
index
Index of the pulse output
0 disables the function
0..4
Increment
Number of pulses to be added to
the reservoir..
Reset command
0 is normal, 1 is no hardware state
changed
0
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range or in
conflict
-
STS
FIOOR
fxPT100Input
Each flow module provides 2 inputs for Pt-100 sensors.
A Pt-100 sensor is a Platinum Resistance Thermometer (PRT) element with a resistance of 100 Ω at 0°C.
'Pt' is the symbol for platinum.
Resistance thermometers as such are also referred to as Resistance Temperature Detectors (RTD).
The resistance changes linearly with temperature. For Pt-100 elements the linearity coefficient is 0.385
Ohm/°C for European elements and 0.392 Ohm/°C for American elements
For each sample the temperature value is obtained from the measured Ohms by means of the standard
RTD quadratic equation.
The input signal is considered to be faulty when the input circuitry has an open or a short circuit or
when the measured value is outside its range (as defined in table below).
Function inputs
Remark
EU
Default
Name
Optional tag name, tag description and tag
group
Channel number
1..2
1
Input Type
1: European, 0.00385 Ω/ Ω /°C
As per DIN 43760, BS1905,IEC751
Range - 200..+850 °C
2: American, 0.00392 Ω/ Ω /°C
Range - 100..+457 °C
1
Содержание flow-x
Страница 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Страница 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Страница 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Страница 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...