7 Configuring example
11.03
7.6 SI I/Os using fail-safe modules connected to PROFIBUS DP
© Siemens AG 2003 All Rights Reserved
7-430
SINUMERIK 840D/SIMODRIVE 611 digital SINUMERIK Safety Integrated (FBSI) - Edition 11.03
Components of the node IM151 HF: F-DI module
The diagram below shows the parameter settings for the F-DI module:
(8) IM 151-1 HF
4 DO 24V/10A
PM-E F DC24V/10A 2 F-DO
4 F-DO DC24V/2A
4/8 F-DI DC24V
PM-E DC24V
6ES7 132-4BD30-0AA0
6ES7 138-4CF00-0AB0
6ES7 138-4FB00-0AA0
6ES7 138-4FA00-0AB0
6ES7 138-4CA00-0AA0
139...143
134...138
128...133
139...143
134...138
128...131
F-Zieladresse 1111111100 (hexadezimal 3FC)
F-Zieladresse 1111111101 (hexadezimal 3FD)
F-Zieladresse 1111111110 (hexadezimal 3FE)
32.0...32.3
Baugruppe
Bestellnummer
E-Adre..... A-Adres.... D..... Kommentar
F_Überwachungszeit (ms)
DIL-Schalterstellung (9........0)
F_Ziel_Adresse
F_Quell_Adresse
F-Parameter
Parameter
100
1111111110
1022
1: SI PLC315-2DP 2AF03
Eigenschaften - 4/8 F-DI DC24V - (R-/S5)
Parameter
Parameter
Adressen
Allgemein
Wert
Kanal 0, 4
Baugruppenparameter
Eingangsverzögerung
Kurzschlusstest
Aktiviert
Auswertung der Geber
Art der Geberverschaltung
Diskrepanzzeit (ms)
Kanal 2, 6
Kanal 1, 5
Kanal 3, 7
2v2-Auswertung
Zweikanalsensor
300
Aktiviert
Auswertung der Geber
Art der Geberverschaltung
Diskrepanzzeit (ms)
2v2-Auswertung
Antivalentsensor
300
OK
Abbrechen
Hilfe
Fig. 7-35
Parameter settings for the F-DI module
The parameters of the F-DO module are explained below:
•
F_Source_Address
The parameter
F_Source_Address
is automatically assigned for the
configured F master (in this case, the NCU 572.4 or NCU 573.4). This
parameter is identical for all PROFIsafe components since they are
associated with the same PROFIsafe master.
•
F_Target_Address
The parameter F_Target_Address is automatically assigned for the
relevant F module and displayed in the decimal notation (for the F-DI
module 1022). The DIL switch setting displayed must be set accordingly.
This address is needed later for parameterizing the machine data in the
hexadecimal notation (for the F-DI module 3FE).
•
F_Monitoring time
The parameter F_Monitoring time defines the maximum time within which a
new valid F telegram must have been received from the F master.
Generally, the default value can be used.
Explanationen of
parameters