5 Commissioning
11.03
5.2 Acceptance report
© Siemens AG 2003 All Rights Reserved
5-284
SINUMERIK 840D/SIMODRIVE 611 digital SINUMERIK Safety Integrated (FBSI) - Edition 11.03
16. Test the SI function "safe cams" – SN
(check using the diagnostics display and assigned SGAs)
17. If necessary, test of SI function "external stops"
in each case with evaluated measurement diagram and measured values.
COMPLETION OF THE REPORT
A report of the commissioning status that was checked is generated with the
appropriate counter-signatures
18. Check the SI machine data
19. Log the checksums (axis MD / SPL)
20. Complete the NCK commissioning
21. Complete the PLC commissioning
22. Verify the data backup
23. Counter-signature.
APPENDIX
Reports/measurement records for FUNCTION TEST PART 1/2
Alarm logs/servo trace measurements
Effect of the acceptance test for specific measures
Table 5-1
Depth of acceptance test as a function of specific measures
Measure DOCUMENT-
ATION
FUNCTION TEST
PART 1
FUNCTION TEST
PART 2
REPORT COMPLETION
Replace the encoder
system
(cf. 7.6.4)
No
No
Partial check of safe
actual values and
function of SE/SN
(axis specific)
No
Upgrade software
(NCU/drive/PLC)
Supplement
version data
Yes
with note about when
the new function is to
be introduced
Yes,
if system cycles or
acceleration behavior
(e.g. also jerk) have
been changed and
the new function tested.
Supplement,
possibly new checksums
and counter-signature
Upgrade software
(MMC)
Possible
supplement,
SW version
No No No
Replace NCU hardware
(e.g. upgrade of
NCU 572 <-> NCU 573)
If the NCU hardware is
identical, no measures
are necessary
Supplement the
hardware data
No Yes,
if system clock cycles
or dynamic response
were changed
Supplement,
possibly new checksums
and counter-signature
Replace control board
(e.g. from Standard.2 <->
Performance)
If control board is
identical, no measures
are necessary
Supplement,
hardware data/
configuration
No Partial,
if the system cycles or
dynamic response were
changed
(axis specific)
Supplement,
possibly new checksums
and counter-signature
Change an individual limit
value (e.g. SG limit)
Supplement,
SI functions per
axis
No Partial,
test the changed limit
value
Supplement,
new checksums and
counter-signature
Function expansion (e.g.
additional actuator,
additional SG stage)
Supplement,
SI functions per
axis or function
table
Yes
with note, if relevant
limited to adapted
parts
Partial,
test of possible
additional limit values
Supplement,
possibly new checksums
and counter-signature