7. COMMUNICATION DATA MAP
54
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
10
DO output distribution
bias
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
0050
0051
0052
0053
0054
0055
0056
0057
80
81
82
83
84
85
86
87
R/W
−
100.0 to
+
100.0 %
0.0
11
DO output distribution
ratio
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
0058
0059
005A
005B
005C
005D
005E
005F
88
89
90
91
92
93
94
95
R/W
−
9.999 to
+
9.999 1.000
12
DO proportional cycle
time
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
0060
0061
0062
0063
0064
0065
0066
0067
96
97
98
99
100
101
102
103
R/W
0.1 to 100.0 seconds
Relay contact
output: 20.0
Open
collector
output: 2.0
13
DO minimum ON/OFF
time of proportioning
cycle
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
0068
0069
006A
006B
006C
006D
006E
006F
104
105
106
107
108
109
110
111
R/W
0 to 1000 ms
0
14
Unused
⎯
0070
・
・
・
00A3
112
・
・
・
163
⎯
⎯
⎯
15
DI function assignment
⎯
00A4
164
R/W
0 to 29
(Refer to page 56)
Based on
model code
When not
specifying: 0
16
Memory area setting
signal
⎯
00A5 165
R/W
0: Validate
1: Invalidate
1
17
DO signal assignment
module address 1
⎯
00A6 166
R/W
−
1, 0 to 99
When “-1” is selected, all of the signals of the
same type (except temperature rise completion
and DO manual output value) are
OR
-operated
and produced as outputs from DO.
−
1
18
DO signal assignment
module address 2
⎯
00A7 167
R/W
−
1, 0 to 99
When “-1” is selected, all of the signals of the
same type (except temperature rise completion
and DO manual output value) are
OR
-operated
and produced as outputs from DO.
−
1
19
DO output assignment 1
[DO1 to DO4]
⎯
00A8
168
R/W
0 to 13
(Refer to page 57)
Based on
model code
When not
specifying: 0
20
DO output assignment 2
[DO5 to DO8]
⎯
00A9
169
R/W
0 to 13
(Refer to page 57)
Based on
model code
When not
specifying: 0
Continued on the next page.