7. COMMUNICATION DATA MAP
38
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
87
Decimal point position
CH1
CH2
CH3
CH4
017E
017F
0180
0181
382
383
384
385
R/W
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
•
K, J, T, E:
Only 0 or 1 can be set.
•
R, S, B, N, PLII, W5Re/W26Re:
Only 0 can be set.
RTD input:
Only 0 or 1 can be set.
Voltage (V)/Current (I) inputs:
From 0 to 4 can be set.
Based on
model code
When not
specifying:
TC/RTD: 1
V/I: 1
88
Input scale high
CH1
CH2
CH3
CH4
0182
0183
0184
0185
386
387
388
389
R/W
TC/RTD inputs:
Input scale low to Maximum value of the
selected
input range
Voltage (V)/Current (I) inputs:
−
19999 to
+
99999
(However, a span is 20000 or less.)
Varies with the setting of the Decimal point position
TC/RTD:
Maximum
value of the
selected
input range
V/I: 100.0
89
Input scale low
CH1
CH2
CH3
CH4
0186
0187
0188
0189
390
391
392
393
R/W
TC/RTD inputs:
Minimum value of the selected input range
to Input scale high
Voltage (V)/Current (I) inputs:
−
19999 to
+
99999
(However, a span is 20000 or less.)
Varies with the setting of the Decimal point
position
TC/RTD:
Minimum
value of the
selected
input range
V/I: 0.0
90
Input error determination
point (high)
CH1
CH2
CH3
CH4
018A
018B
018C
018D
394
395
396
397
R/W
Input error determination point (low) to
(Input range high
+
5 % of Input span)
Input range
high
+
(5 %
of Input span)
91
Input error determination
point (low)
CH1
CH2
CH3
CH4
018E
018F
0190
0191
398
399
400
401
R/W
(Input range low
−
5 % of Input span)
to Input error determination point (high)
Input range
low
−
(5 %
of Input span)
92 Burnout
direction
CH1
CH2
CH3
CH4
0192
0193
0194
0195
402
403
404
405
R/W
0: Upscale
1: Downscale
Valid only when the TC input and Voltage
(low) input are selected.
0
93
Square root extraction
CH1
CH2
CH3
CH4
0196
0197
0198
0199
406
407
408
409
R/W
0: Unused
1: Used
0
94 Output
assignment
(Logic output selection
function)
CH1
CH2
CH3
CH4
019A
019B
019C
019D
410
411
412
413
R/W
0: Control
output
1: Logic output result
2: FAIL output
0
95 Energized/De-energized
(Logic output selection
function)
CH1
CH2
CH3
CH4
019E
019F
01A0
01A1
414
415
416
417
R/W
0: Energized
1: De-energized
0
Continued on the next page.