7. COMMUNICATION DATA MAP
48
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
179 Integrated output limiter
♣
CH1
Unused
CH3
Unused
02EE
Unused
02F0
Unused
750
Unused
752
Unused
R/W
0.0 to 200.0 % of control motor time
(0.0: OFF)
Becomes invalidated when there is Feedback
resistance (FBR) input
150.0
180 Valve action at STOP
♣
CH1
Unused
CH3
Unused
02F2
Unused
02F4
Unused
754
Unused
756
Unused
R/W
0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
Becomes validated when there is no Feedback
resistance (FBR) input or the Feedback
resistance (FBR) input is disconnected.
0
181 ST proportional band
adjusting factor
♣
CH1
CH2
CH3
CH4
02F6
02F7
02F8
02F9
758
759
760
761
R/W
0.01 to 10.00 times
1.00
182 ST integral time adjusting
factor
♣
CH1
CH2
CH3
CH4
02FA
02FB
02FC
02FD
762
763
764
765
R/W
0.01 to 10.00 times
1.00
183 ST derivative time
adjusting factor
♣
CH1
CH2
CH3
CH4
02FE
02FF
0300
0301
766
767
768
769
R/W
0.01 to 10.00 times
1.00
184 ST start condition
♣
CH1
CH2
CH3
CH4
0302
0303
0304
0305
770
771
772
773
R/W
0: Activate the Startup tuning (ST) function
when the power is turned on; when
transferred from STOP to RUN; or when
the Set value (SV) is changed.
1: Activate the Startup tuning (ST) function
when the power is turned on; or when
transferred from STOP to RUN.
2: Activate the Startup tuning (ST) function
when the Set value (SV) is changed.
0
185 Automatic
temperature
rise group
♣
CH1
CH2
CH3
CH4
0306
0307
0308
0309
774
775
776
777
R/W
0 to 16
(0: Automatic temperature rise function OFF)
0
186 Automatic
temperature
rise dead time
♣
CH1
CH2
CH3
CH4
030A
030B
030C
030D
778
779
780
781
R/W
0.1 to 1999.9 seconds
10.0
187 Automatic
temperature
rise gradient data
♣
CH1
CH2
CH3
CH4
030E
030F
0310
0311
782
783
784
785
R/W
0.1 to Input span/minutes
1.0
188 EDS transfer time decimal
point position
♣
CH1
CH2
CH3
CH4
0312
0313
0314
0315
786
787
788
789
R/W
0: 1 second setting (No decimal place)
1: 0.1 seconds setting (One decimal place)
0
189 Output average processing
time for EDS
♣
CH1
CH2
CH3
CH4
0316
0317
0318
0319
790
791
792
793
R/W
0.1 to 200.0 seconds
1.0
190 Responsive action trigger
point for EDS
♣
CH1
CH2
CH3
CH4
031A
031B
031C
031D
794
795
796
797
R/W
0 to Input span (Unit:
°
C [
°
F], %)
1
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.
Содержание COM-JG
Страница 1: ...IMR01Y35 E3 COM JG For SRZ RKC INSTRUMENT INC PROFIBUS Communication Converter Instruction Manual ...
Страница 81: ...8 USAGE EXAMPLE IMR01Y35 E3 75 5 If the PLC is registered the display becomes as follows ...
Страница 125: ...The first edition AUG 2006 IMQ00 The third edition JUL 2010 IMQ00 ...