7. COMMUNICATION DATA MAP
34
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
44 Manual
reset
★
CH1
CH2
CH3
CH4
00B2
00B3
00B4
00B5
178
179
180
181
R/W
−
100.0 to +100.0 %
If the Integral function is validated, set to RO
(Only reading data is possible).
When integral action (heating or cooling side)
is zero, manual reset value is added to the
control output.
0.0
45
Setting change rate limiter
(up)
★
CH1
CH2
CH3
CH4
00B6
00B7
00B8
00B9
182
183
184
185
R/W
0 (0.0) to Input span/unit time *
0 (0.0): Unused
0 (0.0)
46
Setting change rate limiter
(down)
★
CH1
CH2
CH3
CH4
00BA
00BB
00BC
00BD
186
187
188
189
R/W
* Unit time: 60 seconds (factory set value)
0 (0.0)
47
Area soak time
★
CH1
CH2
CH3
CH4
00BE
00BF
00C0
00C1
190
191
192
193
R/W
0 minutes 00 seconds to 199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to 99 hours 59 minutes:
0 to 5999 minuts
Data range of Area soak time can be selected
on the Soak time unit.
0
48
Link area number
★
CH1
CH2
CH3
CH4
00C2
00C3
00C4
00C5
194
195
196
197
R/W
0 to 8
(0: No link)
0
49
Heater break alarm (HBA)
set value
CH1
CH2
CH3
CH4
00C6
00C7
00C8
00C9
198
199
200
201
R/W
When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no Current transformer (CT) or CT is
assigned to “0: None,” set to RO (Only reading
data is possible).
0.0
50 Heater
break
determination point
CH1
CH2
CH3
CH4
00CA
00CB
00CC
00CD
202
203
204
205
R/W
0.0 to 100.0 % of HBA set value
(0.0: Heater break determination is invalidated)
If there is no Current transformer (CT) or CT is
assigned to “0: None,” set to RO (Only reading
data is possible).
If Heater break alarm (HBA) corresponds to
“0: Type A,” set to RO (Only reading data is
possible).
30.0
51 Heater
melting
determination point
CH1
CH2
CH3
CH4
00CE
00CF
00D0
00D1
206
207
208
209
R/W
0.0 to 100.0 % of HBA set value
(0.0: Heater melting determination is invalidated)
If there is no Current transformer (CT) or CT is
assigned to “0: None,” set to RO (Only reading
data is possible).
If Heater break alarm (HBA) corresponds to “0:
Type A,” set to RO (Only reading data is
possible).
30.0
52 PV
bias
CH1
CH2
CH3
CH4
00D2
00D3
00D4
00D5
210
211
212
213
R/W
−
Input span to +Input span
0
53
PV digital filter
CH1
CH2
CH3
CH4
00D6
00D7
00D8
00D9
214
215
216
217
R/W
0.0 to 100.0 seconds
(0.0: Unused)
0.0
54 PV
ratio
CH1
CH2
CH3
CH4
00DA
00DB
00DC
00DD
218
219
220
221
R/W
0.500 to 1.500
1.000
55
PV low input cut-off
CH1
CH2
CH3
CH4
00DE
00DF
00E0
00E1
222
223
224
225
R/W
0.00 to 25.00 % of input span
If the Square root extraction corresponds to “0:
Unused,” set to RO (Only reading data is
possible).
0.00
★
Parameters which can be used in Multi-memory area function.
Continued on the next page.