7. COMMUNICATION DATA MAP
IMR01Y35-E3
33
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
35
Set value (SV)
★
CH1
CH2
CH3
CH4
008E
008F
0090
0091
142
143
144
145
R/W
Setting limiter low to Setting limiter high
TC/RTD: 0
V/I: 0.0
36 Proportional
band
[heat-side]
★
♣
CH1
CH2
CH3
CH4
0092
0093
0094
0095
146
147
148
149
R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the decimal point position
selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool actions
in case of a Heat/Cool PID control type
TC/RTD: 30
V/I: 30.0
37 Integral
time
[heat-side]
★
♣
CH1
CH2
CH3
CH4
0096
0097
0098
0099
150
151
152
153
R/W
PID control or Heat/Cool PID control:
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the Integral/Derivative
time decimal point position selection.
240
38 Derivative
time
[heat-side]
★
♣
CH1
CH2
CH3
CH4
009A
009B
009C
009D
154
155
156
157
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the Integral/Derivative
time decimal point position selection.
60
39 Control
response
parameter
★
♣
CH1
CH2
CH3
CH4
009E
009F
00A0
00A1
158
159
160
161
R/W
0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalidate.
PID control,
Position
proportioning
control: 0
Heat/Cool
PID control: 2
40 Proportional
band
[cool-side]
★
♣
CH1
Unused
CH3
Unused
00A2
Unused
00A4
Unused
162
Unused
164
Unused
R/W
TC/RTD inputs:
1 (0.1) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal point
position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of Input span
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
TC/RTD: 30
V/I: 30.0
41
Integral time [cool-side]
★
♣
CH1
Unused
CH3
Unused
00A6
Unused
00A8
Unused
166
Unused
168
Unused
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
Varies with the setting of the Integral/Derivative
time decimal point position selection.
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
240
42 Derivative
time
[cool-side]
★
♣
CH1
Unused
CH3
Unused
00AA
Unused
00AC
Unused
170
Unused
172
Unused
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the Integral/Derivative
time decimal point position selection.
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
60
43 Overlap/Deadband
★
♣
CH1
CH2
CH3
CH4
00AE
00AF
00B0
00B1
174
175
176
177
R/W
TC/RTD inputs:
−
Input span to +Input span (Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
−
100.0 to +100.0 % of Input span
Minus (
−
) setting results in overlap.
However, the overlapping range is within the
proportional range.
If control is other than Heat/Cool PID control,
set to RO (Only reading data is possible).
0
★
Parameters which can be used in Multi-memory area function.
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.