7. COMMUNICATION DATA MAP
IMR01Y35-E3
49
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
191 Setting change rate limiter
unit time
CH1
CH2
CH3
CH4
031E
031F
0320
0321
798
799
800
801
R/W
1 to 3600 seconds
60
192 Soak time unit
CH1
CH2
CH3
CH4
0322
0323
0324
0325
802
803
804
805
R/W
0: 0 to 5999 minutes
[0 hours 00 minutes to
99 hours 59 minutes]
1: 0 to 11999 seconds
[0 minutes 00 seconds to
199 minutes 59 seconds]
Set the data range of Memory area soak time
monitor and Area soak time.
1
193 Setting limiter high
CH1
CH2
CH3
CH4
0326
0327
0328
0329
806
807
808
809
R/W
Setting limiter low to Input scale high
Input scale
high
194 Setting limiter low
CH1
CH2
CH3
CH4
032A
032B
032C
032D
810
811
812
813
R/W
Input scale low to Setting limiter high
Input scale
low
195 PV transfer function
♣
CH1
CH2
CH3
CH4
032E
032F
0330
0331
814
815
816
817
R/W
0: Unused
1: Used
0
196 Operation mode
assignment 1
(Logic output selection
function)
Logic output 1 to 4
CH1
CH2
CH3
CH4
0332
0333
0334
0335
818
819
820
821
R/W
0: No
assignment
1: Operation mode (monitor, control)
2: Operation
mode
(monitor, event function, control)
3: Auto/Manual
4: Remote/Local
5: Unused (Do not set this one)
0
197 Operation mode
assignment 2
(Logic output selection
function)
Logic output 5 to 8
CH1
CH2
CH3
CH4
0336
0337
0338
0339
822
823
824
825
R/W
0: No
assignment
1: Operation mode (monitor, control)
2: Operation
mode
(monitor, event function, control)
3: Auto/Manual
4: Remote/Local
5: Unused (Do not set this one)
0
198 SV select function
CH1
CH2
CH3
CH4
033A
033B
033C
033D
826
827
828
829
R/W
0: Remote SV function
1: Cascade control function
2: Ratio setting function
3: Cascade control 2 function
0
199 Remote SV function
master channel module
address
CH1
CH2
CH3
CH4
033E
033F
0340
0341
830
831
832
833
R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
−
1
200 Remote SV function
master channel selection
CH1
CH2
CH3
CH4
0342
0343
0344
0345
834
835
836
837
R/W
1 to 99
1
201 Output distribution master
channel module address
CH1
CH2
CH3
CH4
0346
0347
0348
0349
838
839
840
841
R/W
−
1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
−
1
202 Output distribution master
channel selection
CH1
CH2
CH3
CH4
034A
034B
034C
034D
842
843
844
845
R/W
1 to 99
1
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.