7. COMMUNICATION DATA MAP
44
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
129 Start determination point
CH1
CH2
CH3
CH4
0226
0227
0228
0229
550
551
552
553
R/W
0 to Input span
(The unit is the same as input value.)
(0: Action depending on the Hot/Cold start
selection)
Based on
specification
130 SV tracking
CH1
CH2
CH3
CH4
022A
022B
022C
022D
554
555
556
557
R/W
0: Unused
1: Used
1
131 MV transfer function
[Action taken when
changed to Manual mode
from Auto mode]
CH1
CH2
CH3
CH4
022E
022F
0230
0231
558
559
560
561
R/W
0: MV in Auto mode is used.
[Balanceless-bumpless function]
1: MV in previous Manual mode is used.
0
132 Control
action
CH1
CH2
CH3
CH4
0232
0233
0234
0235
562
563
564
565
R/W
0: Brilliant II PID control (Direct action)
1: Brilliant II PID control (Reverse action)
2: Brilliant II Heat/Cool PID control
[Water cooling type]
3: Brilliant II Heat/Cool PID control
[Air cooling type]
4: Brilliant II Heat/Cool PID control
[Cooling gain linear type]
5: Position proportioning control
Odd channel: From 0 to 5 can be set.
Even channel: Only 0 or 1 can be set.
Based on
model code
When not
specifying: 1
133 Integral/Derivative
time
decimal point position
♣
CH1
CH2
CH3
CH4
0236
0237
0238
0239
566
567
568
569
R/W
0: 1 second setting (No decimal place)
1: 0.1 seconds setting (One decimal place)
0
134 Derivative
action
♣
CH1
CH2
CH3
CH4
023A
023B
023C
023D
570
571
572
573
R/W
0: Measured value derivative
1: Deviation derivative
0
135 Undershoot
suppression
factor
♣
CH1
Unused
CH3
Unused
023E
Unused
0240
Unused
574
Unused
576
Unused
R/W
0.000 to 1.000
Water cooling:
0.100
Air cooling:
0.250
Cooling gain
linear type:
1.000
136 Derivative
gain
♣
CH1
CH2
CH3
CH4
0242
0243
0244
0245
578
579
580
581
R/W
0.1 to 10.0
6.0
137 ON/OFF
action
differential gap (upper)
♣
CH1
CH2
CH3
CH4
0246
0247
0248
0249
582
583
584
585
R/W
TC/RTD: 1
V/I: 0.1
138 ON/OFF
action
differential gap (lower)
♣
CH1
CH2
CH3
CH4
024A
024B
024C
024D
586
587
588
589
R/W
TC/RTD inputs:
0 to Input span (Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
0.0 to 100.0 % of input span
TC/RTD: 1
V/I: 0.1
139 Action (high) at input
error
♣
CH1
CH2
CH3
CH4
024E
024F
0250
0251
590
591
592
293
R/W
0: Normal control
1: Manipulated output value at input error
0
140 Action (low) at input
error
♣
CH1
CH2
CH3
CH4
0252
0253
0254
0255
594
595
596
597
R/W
0
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.