8. USAGE EXAMPLE
IMR01Y35-E3
85
4.
Set read and write items in order from “Group 1 ID (base ten).”
The set value sets the Modbus register address of the controller (SRZ) connected in a decimal
number. In this example, make the setting as follows.
Read item: Group 1 ID (base ten): 65024 (No. 1 Number of continuous accesses)
Write item: Group 2 ID (base ten): 65024 (No. 1 Number of continuous accesses)
Because the number of read items is set to “1,” a read item can only be set for Group 1 ID
(base ten). Write items must be set for Group 2 ID (base ten) and following groups.
Blank items will be the factory set value “65535.”
For Modbus register address of COM-JG initial setting items, refer to
7.5
COM-JG
Initial Setting Items
(P. 58)
.
5.
After the allocation of data parameters is finished, click “OK.”
Set “65024: No. 1 Number
of continuous
accesses” as
the read item.
Set “65024: No. 1 Number
of continuous accesses” as
the write item.
Содержание COM-JG
Страница 1: ...IMR01Y35 E3 COM JG For SRZ RKC INSTRUMENT INC PROFIBUS Communication Converter Instruction Manual ...
Страница 81: ...8 USAGE EXAMPLE IMR01Y35 E3 75 5 If the PLC is registered the display becomes as follows ...
Страница 125: ...The first edition AUG 2006 IMQ00 The third edition JUL 2010 IMQ00 ...