7. COMMUNICATION DATA MAP
IMR01Y35-E3
41
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
107 Event 2 differential gap
CH1
CH2
CH3
CH4
01CE
01CF
01D0
01D1
462
463
464
465
R/W
c
Deviation, process, set value, or Deviation
action between channels:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
c
: 1
d
: 1.0
108 Event 2 delay timer
CH1
CH2
CH3
CH4
01D2
01D3
01D4
01D5
466
467
468
469
R/W
0 to 18000 seconds
0
109 Force ON of Event 2 action
CH1
CH2
CH3
CH4
01D6
01D7
01D8
01D9
470
471
472
473
R/W
Bit data
Bit 0: Event output turned on at input error
occurrence
Bit 1: Event output turned on in manual mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the Setting
change rate limiter isbeing operated
Bit 4 to Bit 15: Unused
Data
0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
110 Event 3 type
CH1
CH2
CH3
CH4
01DA
01DB
01DC
01DD
474
475
476
477
R/W
0: None
1: Deviation high (SV monitor value used)
1
2: Deviation low (SV monitor value used)
1
3: Deviation high/low (SV monitor value used)
1
4: Band (SV monitor value used)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Temperature rise completion
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high (Local SV value used)
1
15: Deviation low (Local SV value used)
1
16: Deviation high/low (Local SV value used)
1
17: Deviation (Local SV value used)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning control, set to the
Feedback resistance (FBR) input value.
Based on
model code
When not
specifying: 0
111 Event 3 channel setting
CH1
CH2
CH3
CH4
01DE
01DF
01E0
01E1
478
479
480
481
R/W
1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is validated when “Deviation
between channels” is selected
1
112 Event 3 hold action
CH1
CH2
CH3
CH4
01E2
01E3
01E4
01E5
482
483
484
485
R/W
0: OFF
1: Hold action ON
(when power turned on; when transferred
from STOP to RUN)
2: Re-hold action ON
(when power turned on; when transferred
from STOP to RUN; SV changed)
This function is validated when input value,
deviation or manipulated value action has been
selected.
In case of a deviation action, this function is
not available while in Remote mode and while
Setting changing rate limiter is working.
Based on
model code
When not
specifying:
0
Continued on the next page.