7. COMMUNICATION DATA MAP
42
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
113 Event 3 interlock
CH1
CH2
CH3
CH4
01E6
01E7
01E8
01E9
486
487
488
489
R/W
0: Unused
1: Used
0
114 Event 3 differential gap
CH1
CH2
CH3
CH4
01EA
01EB
01EC
01ED
490
491
492
493
R/W
c
Deviation, process, set value, Deviation
action between channels, or Temperature
rise completion:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
c
: 1
d
: 1.0
115 Event 3 delay timer
CH1
CH2
CH3
CH4
01EE
01EF
01F0
01F1
494
495
496
497
R/W
0 to 18000 seconds
If Event 3 corresponds to “9: Temperature rise
completion,” the Event 3 delay timer becomes
the temperature rise completion soak time.
0
116 Force ON of Event 3 action
CH1
CH2
CH3
CH4
01F2
01F3
01F4
01F5
498
499
500
501
R/W
Bit data
Bit 0: Event output turned on at input error
occurrence
Bit 1: Event output turned on in manual mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the Setting
change rate limiter isbeing operated
Bit 4 to Bit 15: Unused
Data
0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
117 Event 4 type
CH1
CH2
CH3
CH4
01F6
01F7
01F8
01F9
502
503
504
505
R/W
0: None
1: Deviation high (SV monitor value used)
1
2: Deviation low (SV monitor value used)
1
3: Deviation high/low (SV monitor value used)
1
4: Band (SV monitor value used)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Control loop break alarm (LBA)
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high (Local SV value used)
1
15: Deviation low (Local SV value used)
1
16: Deviation high/low (Local SV value used)
1
17: Deviation (Local SV value used)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning control, set to the
Feedback resistance (FBR) input value.
Based on
model code
When not
specifying: 0
118 Event 4 channel setting
CH1
CH2
CH3
CH4
01FA
01FB
01FC
01FD
506
507
508
509
R/W
1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is validated when “Deviation
between channels” is selected
1
Continued on the next page.