7. COMMUNICATION DATA MAP
IMR01Y35-E3
35
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
56
RS bias *
CH1
CH2
CH3
CH4
00E2
00E3
00E4
00E5
226
227
228
229
R/W
−
Input span to +Input span
0
57
RS digital filter *
CH1
CH2
CH3
CH4
00E6
00E7
00E8
00E9
230
231
232
233
R/W
0.0 to 100.0 seconds
(0.0: Unused)
0.0
58
RS ratio *
CH1
CH2
CH3
CH4
00EA
00EB
00EC
00ED
234
235
236
237
R/W
0.001 to 9.999
1.000
59 Output
distribution
selection
CH1
CH2
CH3
CH4
00EE
00EF
00F0
00F1
238
239
240
241
R/W
0: Control output
1: Distribution output
0
60
Output distribution bias
CH1
CH2
CH3
CH4
00F2
00F3
00F4
00F5
242
243
244
245
R/W
−
100.0 to
+
100.0 %
0.0
61
Output distribution ratio
CH1
CH2
CH3
CH4
00F6
00F7
00F8
00F9
246
247
248
249
R/W
−
9.999 to
+
9.999 1.000
62
Proportional cycle time
CH1
CH2
CH3
CH4
00FA
00FB
00FC
00FD
250
251
252
253
R/W
0.1 to 100.0 seconds
This item becomes RO (Only reading data is
possible) for the Voltage/Current output
specification.
This parameter is validated when "0: control
output" has been selected at No.94 "Output
assignment".
Relay contact
output: 20.0
Voltage pulse
output, Triac
output and
Open collector
output: 2.0
63
Minimum ON/OFF time
of proportioning cycle
CH1
CH2
CH3
CH4
00FE
00FF
0100
0101
254
255
256
257
R/W
0 to 1000 ms
This item becomes RO (Only reading data is
possible) for the Voltage/Current output
specification.
0
64 Manual
manipulated
output value
♣
CH1
CH2
CH3
CH4
0102
0103
0104
0105
258
259
260
261
R/W
PID control:
Output limiter low to Output limiter high
Heat/Cool PID control:
−
Cool-side output limiter (high) to
+
Heat-side output limiter (high)
Position proportioning control:
When there is Feedback resistance (FBR) input
and it does not break:
Output limiter low to Output limiter high
When there is no Feedback resistance (FBR)
input or the Feedback resistance (FBR) input is
disconnected:
0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
0.0
65
Area soak time stop
function
CH1
CH2
CH3
CH4
0106
0107
0108
0109
262
263
264
265
R/W
0: No function
1: Event 1
2: Event 2
3: Event 3
4: Event 4
0
* Data on RS bias, RS ratio and RS digital filter is that in cascade control or ratio setting.
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.