8. USAGE EXAMPLE
IMR01Y35-E3
94
6.
Set the static data read request items.
In the configuration settings, the PLC register addresses of the static data read request item
(“Static input word”) are set as follows:
Input Start address (I Address): 10
End address (I Address): 17 (Automatically assigned)
As such, set “IW10,” “IW12,” “IW14,” and “IW16” in “Address” of the variable table.
(IW10: A one-byte data area [address 10 and 11] is allocated in address 10 and the data of address
10 is read.)
7.
Change the display format of “IW10,” “IW12,” “IW14,” and “IW16” from HEX to DEC.
Right-click a cell that shows HEX and select “Decimal” from the sub-menu to change to DEC.
Right-click