7. COMMUNICATION DATA MAP
40
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
102 Force ON of Event 1 action
CH1
CH2
CH3
CH4
01BA
01BB
01BC
01BD
442
443
444
445
R/W
Bit data
Bit 0: Event output turned on at input error
occurrence
Bit 1: Event output turned on in manual mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the Setting
change rate limiter isbeing operated
Bit 4 to Bit 15: Unused
Data
0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
103 Event 2 type
CH1
CH2
CH3
CH4
01BE
01BF
01C0
01C1
446
447
448
449
R/W
0: None
1: Deviation high (SV monitor value used)
1
2: Deviation low (SV monitor value used)
1
3: Deviation high/low (SV monitor value used)
1
4: Band (SV monitor value used)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Unused
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high (Local SV value used)
1
15: Deviation low (Local SV value used)
1
16: Deviation high/low (Local SV value used)
1
17: Deviation (Local SV value used)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning control, set to the
Feedback resistance (FBR) input value.
Based on
model code
When not
specifying: 0
104 Event 2 channel setting
CH1
CH2
CH3
CH4
01C2
01C3
01C4
01C5
450
451
452
453
R/W
1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is validated when “Deviation
between channels” is selected
1
105 Event 2 hold action
CH1
CH2
CH3
CH4
01C6
01C7
01C8
01C9
454
455
456
457
R/W
0: OFF
1: Hold action ON
(when power turned on; when transferred
from STOP to RUN)
2: Re-hold action ON
(when power turned on; when transferred
from STOP to RUN; SV changed)
This function is validated when input value,
deviation or manipulated value action has been
selected.
In case of a deviation action, this function is
not available while in Remote mode and while
Setting changing rate limiter is working.
Based on
model code
When not
specifying:
0
106 Event 2 interlock
CH1
CH2
CH3
CH4
01CA
01CB
01CC
01CD
458
459
460
461
R/W
0: Unused
1: Used
0
Continued on the next page.
Содержание COM-JG
Страница 1: ...IMR01Y35 E3 COM JG For SRZ RKC INSTRUMENT INC PROFIBUS Communication Converter Instruction Manual ...
Страница 81: ...8 USAGE EXAMPLE IMR01Y35 E3 75 5 If the PLC is registered the display becomes as follows ...
Страница 125: ...The first edition AUG 2006 IMQ00 The third edition JUL 2010 IMQ00 ...