7. COMMUNICATION DATA MAP
IMR01Y35-E3
39
Continued from the previous page.
Modbus
register address
No. Name
Channe
l
HEX DEC
Attri-
bute
Data range
Factory
set value
96
Event 1 type
CH1
CH2
CH3
CH4
01A2
01A3
01A4
01A5
418
419
420
421
R/W
0: None
1: Deviation high (Using SV monitor value)
1
2: Deviation low (Using SV monitor value)
1
3: Deviation high/low (Using SV monitor value)
1
4: Band (Using SV monitor value)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Unused
10: MV high [heat-side]
1, 2
11: MV low [heat-side]
1, 2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high (Using local SV)
1
15: Deviation low (Using local SV)
1
16: Deviation high/low (Using local SV)
1
17: Deviation (Using local SV)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels high/low
1
21: Deviation between channels band
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning control, set to the
Feedback resistance (FBR) input value.
Based on
model code
When not
specifying:
0
97
Event 1 channel setting
CH1
CH2
CH3
CH4
01A6
01A7
01A8
01A9
422
423
424
425
R/W
1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is validated when “Deviation
between channels” is selected
1
98
Event 1 hold action
CH1
CH2
CH3
CH4
01AA
01AB
01AC
01AD
426
427
428
429
R/W
0: OFF
1: Hold action ON
(when power turned on; when transferred
from STOP to RUN)
2: Re-hold action ON
(when power turned on; when transferred
from STOP to RUN; SV changed)
This function is validated when input value,
deviation or manipulated value action has been
selected.
In case of a deviation action, this function is
not available while in Remote mode and while
Setting changing rate limiter is working.
Based on
model code
When not
specifying:
0
99
Event 1 interlock
CH1
CH2
CH3
CH4
01AE
01AF
01B0
01B1
430
431
432
433
R/W
0: Unused
1: Used
0
100 Event 1 differential gap
CH1
CH2
CH3
CH4
01B2
01B3
01B4
01B5
434
435
436
437
R/W
c
Deviation, process, set value, or Deviation
action between channels:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
c
: 1
d
: 1.0
101 Event 1 delay timer
CH1
CH2
CH3
CH4
01B6
01B7
01B8
01B9
438
439
440
441
R/W 0 to 18000 seconds
0
Continued on the next page.