5. SETTING
IMR01Y35-E3
19
5.4 Controller Address Auto Obtain Methods
To allow the PLC and COM-JG to communicate, the COM-JG must be made to recognize the address
of each controller (the module addresses of the SRZ).
Although the PLC configuration tool can be used to configure settings to make the COM-G recognize
the controller addresses, the DIP switches can be set to have the settings configured automatically.
For setting method using the PLC configuration tool, refer to
5.3
COM-JG Initial Setting
(P. 17),
8.4 Contents Check of COM-JG Initial Setting
(P. 63)
and
8.5 PLC Tool Setting (P. 70)
.
Procedure
This procedure assumes that the controller (SRZ) communication settings have been
completed.
To execute controller address auto obtain, DIP switch No. 7 on the left side of the COM-JG
must be set to OFF (controller communication enabled).
1.
Set DIP switch No. 4 on the left side of the COM-JG to ON (auto obtain ON).
Set the controller communication speed with DIP switch Nos. 1 and 2.
Set the controller communication speed to the same value as the controller (SRZ) setting.
For the DIP switch setting, refer to
5.2 DIP Switch Setting (P. 16)
.
DIP switch
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
OFF
ON: Auto obtain ON
Controller communication
speed setting
(19200 bps)
2.
Connect the power wiring and the wiring between the COM-JG and the controllers (SRZ).
There is no need for the COM-JG to be connected to the PROFIBUS when controller
address auto obtain is executed.