7. COMMUNICATION DATA MAP
46
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
154 Output value with AT
turned on
♣
CH1
CH2
CH3
CH4
028A
028B
028C
028D
650
651
652
653
R/W
Output value with AT turned off to 105.0 %
Actual output values become those restricted
by the output limiter.
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it does
not break (high limit of feedback resistance
input at AT).
105.0
155 Output value with AT
turned off
♣
CH1
CH2
CH3
CH4
028E
028F
0290
0291
654
655
656
657
R/W
−
105.0 % to Output value with AT turned on
Actual output values become those restricted
by the output limiter.
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it does
not break (low limit of feedback resistance
input at AT).
−
105.0
156 AT differential gap time
♣
CH1
CH2
CH3
CH4
0292
0293
0294
0295
658
659
660
661
R/W
0.0 to 50.0 seconds
10.0
157 Proportional band
adjusting factor
[heat-side]
♣
CH1
CH2
CH3
CH4
0296
0297
0298
0299
662
663
664
665
R/W
0.01 to 10.00 times
1.00
158 Integral time adjusting
factor [heat-side]
♣
CH1
CH2
CH3
CH4
029A
029B
029C
029D
666
667
668
669
R/W
0.01 to 10.00 times
1.00
159 Derivative time adjusting
factor [heat-side]
♣
CH1
CH2
CH3
CH4
029E
029F
02A0
02A1
670
671
672
673
R/W
0.01 to 10.00 times
1.00
160 Proportional band
adjusting factor
[cool-side]
♣
CH1
Unused
CH3
Unused
02A2
Unused
02A4
Unused
674
Unused
676
Unused
R/W
0.01 to 10.00 times
1.00
161 Integral time adjusting
factor [cool-side]
♣
CH1
Unused
CH3
Unused
02A6
Unused
02A8
Unused
678
Unused
680
Unused
R/W
0.01 to 10.00 times
1.00
162 Derivative time adjusting
factor [cool-side]
♣
CH1
Unused
CH3
Unused
02AA
Unused
02AC
Unused
682
Unused
684
Unused
R/W
0.01 to 10.00 times
1.00
163 Proportional band limiter
(high) [heat-side]
♣
CH1
CH2
CH3
CH4
02AE
02AF
02B0
02B1
686
687
688
689
R/W
TC/RTD:
Input span
V/I: 1000.0
164 Proportional band limiter
(low) [heat-side]
♣
CH1
CH2
CH3
CH4
02B2
02B3
02B4
02B5
690
691
692
693
R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal point
position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool actions
in case of a Heat/Cool control type.)
TC/RTD:
0 (0.0)
V/I: 0.0
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.