7. COMMUNICATION DATA MAP
IMR01Y35-E3
43
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
119 Event 4 hold action
CH1
CH2
CH3
CH4
01FE
01FF
0200
0201
510
511
512
513
R/W
0: OFF
1: Hold action ON
(when power turned on; when transferred
from STOP to RUN)
2: Re-hold action ON
(when power turned on; when transferred
from STOP to RUN; SV changed)
This function is validated when input value,
deviation or manipulated value action has been
selected.
In case of a deviation action, this function is
not available while in Remote mode and while
Setting changing rate limiter is working.
Based on
model code
When not
specifying:
0
120 Event 4 interlock
CH1
CH2
CH3
CH4
0202
0203
0204
0205
514
515
516
517
R/W
0: Unused
1: Used
0
121 Event 4 differential gap
CH1
CH2
CH3
CH4
0206
0207
0208
0209
518
519
520
521
R/W
c
Deviation, process, set value, or Deviation
action between channels:
0 to Input span (Unit:
°
C [
°
F])
d
MV: 0.0 to 110.0 %
Becomes invalidated when the Event 4 type
corresponds to “9: Control loop break alarm
(LBA).”
c
: 1
d
: 1.0
122 Event 4 delay timer
CH1
CH2
CH3
CH4
020A
020B
020C
020D
522
523
524
525
R/W
0 to 18000 seconds
0
123 Force ON of Event 4 action
CH1
CH2
CH3
CH4
020E
020F
0210
0211
526
527
528
529
R/W
Bit data
Bit 0: Event output turned on at input error
occurrence
Bit 1: Event output turned on in manual mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the Setting
change rate limiter isbeing operated
Bit 4 to Bit 15: Unused
Data
0: Invalidate
1: Validate
[Decimal number: 0 to 15]
0
124 CT
ratio
CH1
CH2
CH3
CH4
0212
0213
0214
0215
530
531
532
533
R/W 0 to 9999
CTL-6-P-N:
800
CTL-12-S56-
10L-N:
1000
125 CT
assignment
CH1
CH2
CH3
CH4
0216
0217
0218
0219
534
535
536
537
R/W 0: None
1: OUT1
2: OUT2
3: OUT3
4: OUT4
1
126 Heater break alarm (HBA)
type
CH1
CH2
CH3
CH4
021A
021B
021C
021D
538
539
540
541
R/W
0: Heater break alarm (HBA) type A
(Time-proportional control output)
1: Heater break alarm (HBA) type B
(Continuous control output)
Based on
model code
127 Number of heater break
alarm (HBA) delay times
CH1
CH2
CH3
CH4
021E
021F
0220
0221
542
543
544
545
R/W
0 to 255 times
5
128 Hot/Cold start
CH1
CH2
CH3
CH4
0222
0223
0224
0225
546
547
548
549
R/W
0: Hot start 1
1: Hot start 2
2: Cold
start
0
Continued on the next page.