7. COMMUNICATION DATA MAP
IMR01Y35-E3
45
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
141 Manipulated output value
at input error
♣
CH1
CH2
CH3
CH4
0256
0257
0258
0259
598
599
600
601
R/W
−
105.0 to
+
105.0 %
Actual output values become those restricted
by the output limiter.
Position proportioning control:
If there is no Feedback resistance (FBR)
input or the Feedback resistance (FBR) input
is disconnected, an action taken when
abnormal is in accordance with the value
action setting during STOP.
0.0
142 Manipulated output value
at STOP mode [heat-side]
♣
CH1
CH2
CH3
CH4
025A
025B
025C
025D
602
603
604
605
R/W
−
5.0
143 Manipulated output value
at STOP mode [cool-side]
♣
CH1
Unused
CH3
Unused
025E
Unused
0260
Unused
606
Unused
608
Unused
R/W
−
5.0 to
+
105.0 %
Position proportioning control:
Only when there is Feedback resistance
(FBR) input and it does not break, the
Manipulated output value [heat-side] at
STOP is output.
−
5.0
144 Output change rate limiter
(up) [heat-side]
♣
CH1
CH2
CH3
CH4
0262
0263
0264
0265
610
611
612
613
R/W
0.0
145 Output change rate limiter
(down) [heat-side]
♣
CH1
CH2
CH3
CH4
0266
0267
0268
0269
614
615
616
617
R/W
0.0 to 100.0 %/seconds
(0.0: OFF)
Becomes invalidated when in Position
proportioning control.
0.0
146 Output limiter high
[heat-side]
♣
CH1
CH2
CH3
CH4
026A
026B
026C
026D
618
619
620
621
R/W
Output limiter low to 105.0 %
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it does
not break.
105.0
147 Output limiter low
[heat-side]
♣
CH1
CH2
CH3
CH4
026E
026F
0270
0271
622
623
624
625
R/W
−
5.0 % to Output limiter high
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it does
not break.
−
5.0
148 Output change rate limiter
(up) [cool-side]
♣
CH1
Unused
CH3
Unused
0272
Unused
0274
Unused
626
Unused
628
Unused
R/W
0.0
149 Output change rate limiter
(down) [cool-side]
♣
CH1
Unused
CH3
Unused
0276
Unused
0278
Unused
630
Unused
632
Unused
R/W
0.0 to 100.0 %/seconds
(0.0: OFF)
Becomes invalidated when in Position
proportioning control.
0.0
150 Output limiter high
[cool-side]
♣
CH1
Unused
CH3
Unused
027A
Unused
027C
Unused
634
Unused
636
Unused
R/W
Output limiter low [cool-side] to 105.0 %
105.0
151 Output limiter low
[cool-side]
♣
CH1
Unused
CH3
Unused
027E
Unused
0280
Unused
638
Unused
640
Unused
R/W
−
5.0 % to Output limiter high [cool-side]
−
5.0
152 AT
bias
♣
CH1
CH2
CH3
CH4
0282
0283
0284
0285
642
643
644
645
R/W
−
Input span to +Input span
0
153 AT
cycles
♣
CH1
CH2
CH3
CH4
0286
0287
0288
0289
646
647
648
649
R/W
0: 1.5
cycles
1: 2.0
cycles
2: 2.5
cycles
3: 3.0
cycles
1
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.