7. COMMUNICATION DATA MAP
IMR01Y35-E3
51
7.3 Memory Area Data of Z-TIO Module
The register addresses, 0500H to 0553H are used for checking and changing each set value belonging to the
memory area.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
1
Setting memory area
number
CH1
CH2
CH3
CH4
0500
0501
0502
0503
1280
1281
1282
1283
R/W
1 to 8
1
2
Event 1 set value (EV1)
CH1
CH2
CH3
CH4
0504
0505
0506
0507
1284
1285
1286
1287
R/W
50
3
Event 2 set value (EV2)
CH1
CH2
CH3
CH4
0508
0509
050A
050B
1288
1289
1290
1291
R/W
50
4
Event 3 set value (EV3)
CH1
CH2
CH3
CH4
050C
050D
050E
050F
1292
1293
1294
1295
R/W
50
5
Event 4 set value (EV4)
CH1
CH2
CH3
CH4
0510
0511
0512
0513
1296
1297
1298
1299
R/W
Deviation action,
Deviation action between channels,
Temperatue rise completion range:
−
Input span to +Input span
Process action, SV action:
Input scale low to Input scale high
MV action:
−
5.0 to
+
105.0 %
50
6
Control loop break alarm
(LBA) time
CH1
CH2
CH3
CH4
0514
0515
0516
0517
1300
1301
1302
1303
R/W
0 to 7200 seconds
(0: Unused)
480
7 LBA
deadband
CH1
CH2
CH3
CH4
0518
0519
051A
051B
1304
1305
1306
1307
R/W
0 (0.0) to Input span
0 (0.0)
8
Set value (SV)
CH1
CH2
CH3
CH4
051C
051D
051E
051F
1308
1309
1310
1311
R/W
Setting limiter low to Setting limiter high
TC/RTD: 0
V/I: 0.0
9 Proportional
band
[heat-side]
CH1
CH2
CH3
CH4
0520
0521
0522
0523
1312
1313
1314
1315
R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool actions
in case of a Heat/Ccool PID control type.)
TC/RTD: 30
V/I: 30.0
10
Integral time [heat-side]
CH1
CH2
CH3
CH4
0524
0525
0526
0527
1316
1317
1318
1319
R/W
PID control or Heat/Ccool PID control:
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
240
11 Derivative
time
[heat-side]
CH1
CH2
CH3
CH4
0528
0529
052A
052B
1320
1321
1322
1323
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
60
12 Control
response
parameter
CH1
CH2
CH3
CH4
052C
052D
052E
052F
1324
1325
1326
1327
R/W
0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalidate.
PID control,
Position
proportioning
control: 0
Heat/Cool
PID control: 2
13 Proportional
band
[cool-side]
CH1
CH2
CH3
CH4
0530
0531
0532
0533
1328
1329
1330
1331
R/W
TC/RTD inputs:
1 to Input span or 0.1 to Input span
(Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of Input span
TC/RTD: 30
V/I: 30.0
Continued on the next page.