7. COMMUNICATION DATA MAP
30
IMR01Y35-E3
7.2 Communication Data of Z-TIO Module
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
1
Measured value (PV)
CH1
CH2
CH3
CH4
0000
0001
0002
0003
0
1
2
3
RO
Input scale low to Input scale high
⎯
2 Comprehensive
event
state
CH1
CH2
CH3
CH4
0004
0005
0006
0007
4
5
6
7
RO
Bit data
Bit 0: Event 1 state
Bit 1: Event 2 state
Bit 2: Event 3 state
Bit 3: Event 4 state
Bit 4: Heater break alarm state
Bit 5: Temperature rise completion
Bit 6: Burnout
Bit 7 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 127]
⎯
3
Operation mode state
monitor
CH1
CH2
CH3
CH4
0008
0009
000A
000B
8
9
10
11
RO
Bit data
Bit 0: Control STOP
Bit 1: Control RUN
Bit 2: Manual mode *
Bit 3: Remote mode *
Bit 4 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 15]
* During operation in manual mode, the manual
mode of the operation mode state monitor is
set to the “1: ON” state and the remote mode
of the same monitor is se to the “0: OFF”
state even if the parameter, “Remote/Local
transfer” is set to “1: Remote mode.”
⎯
4 Error
code
⎯
000C 12 RO
Bit
data
Bit 0: Adjustment data error
Bit 1: Data back-up error
Bit 2: A/D conversion error
Bit 3: Unused
Bit 4: Unused
Bit 5: Logic output data error
Bit 6 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 63]
If two or more errors occur simultaneously, the
total summation of these error codes is displayed.
⎯
5
Manipulated output value
(MV) monitor [heat-side]
♣
CH1
CH2
CH3
CH4
000D
000E
000F
0010
13
14
15
16
RO
PID control or Heat/Cool PID control:
−
5.0 to
+
105.0 %
Position proportioning control with feedback
resistance (FBR) input:
0.0 to 100.0 %
⎯
6
Manipulated output value
(MV) monitor [cool-side]
♣
CH1
Unused
CH3
Unused
0011
Unused
0012
Unused
17
Unused
19
Unused
RO
−
5.0 to
+
105.0 %
⎯
7
Current transformer (CT)
input value monitor
CH1
CH2
CH3
CH4
0015
0016
0017
0018
21
22
23
24
RO
CTL-6-P-N:
0.0 to 30.0A
CTL-12-S56-10L-N: 0.0 to 100.0 A
⎯
8
Set value (SV) monitor
CH1
CH2
CH3
CH4
0019
001A
001B
001C
25
26
27
28
RO
Setting limiter low to Setting limiter high
⎯
♣
Parameters only used for Heat/Cool PID control or Position proportioning control, therefore data for CH2 and CH4 of
Z-TIO modules are unused.
Continued on the next page.