4. WIRING
IMR01Y35-E3
12
4.4 Connection to the Controllers
Conduct wiring between the COM-JG and controller (SRZ) as shown in the following.
SRZ (Z-TIO module/Z-DIO module) communication terminal number and
signal details
Terminal No.
Signal name
Symbol
3
Send/Receive data
T/R (A)
4
Send/Receive data
T/R (B)
5 Signal
ground
SG
Wiring
RS-485
Paired
wire
Shielded twisted
pair wire
Controller (SRZ)
Up to 16 Z-TIO modules can be connected.
R2
R2: Termination resistor for external
connection
(120
Ω
1/2
W)
3
4
5 SG
COM-JG
SG
1
5
4
R1
Terminal block
T/R (A)
T/R (B)
3
4
5 SG
T/R (B)
T/R (A)
T/R (B)
T/R (A)
Z-TIO module
Z-TIO module
Connected by
the internal
communication
line
R1: Internal termination resistor
(Example:
120
Ω
1/2 W)
(
+
)
(
−
)
(
+
)
(
−
)
(
+
)
(
−
)
The cable and termination resistor(s) must be provided by the customer.
A combined total of up to 31 Z-TIO and Z-DIO modules can be connected in the SRZ,
however, in some cases this may not be possible due to restrictions related to the number of
connected channels and communication items.
[ Refer to
6.2.1 Data type and data length of communication data (P. 22)
]
3 4 5
2
1
SRZ base section
Communication
terminal No.
For termination resistors, refer to
4.5 Installation of Termination
Resistor (P. 13)