10. SPECIFICATIONS
IMR01Y35-E3
117
117
Self-diagnostic function
Hardware error:
Display: FAIL lamp ON
Configuration error (Can not recognize the controller):
Display: RUN lamp flashes
Status: Set bit 0 of an error state register
Memory backup error:
Display: RUN lamp flashes
Status: Set bit 0 of an error state register
General specifications
Power supply voltage:
21.6 to 26.4 V DC [Including power supply voltage variation]
(Rating 24 V DC)
Current consumption:
90 mA max. (at 24 V DC)
Rush current:
12 A or less
Insulation resistance:
Between communication terminal and grounding:
20
M
Ω
or more at 500 V DC
Between power supply terminal and grounding:
20
M
Ω
or more at 500 V DC
Between power supply terminal and communication terminal:
20
M
Ω
or more at 500 V DC
Withstand voltage:
Refer to table shown below
Time: 1 min.
Grounding terminal
Power supply terminal
600 V AC
Communication terminal 600 V AC 600 V AC
Power failure:
A power failure of 20 ms or less will not affect the action.
Data backup:
Data backed up by non-volatile memory
Number of writing: Approx. 100,000 times.
Data storage period: Approx. 10 years
Vibration:
Amplitude:
<
1.5 mm (5 to 9 Hz)
Acceleration:
<
5 m/s
2
(9 to150 Hz)
Each direction of XYZ axes
Shock:
Height 50 mm or less
Each direction of XYZ axes (de-energized state)
Allowable ambient temperature:
−
10 to
+
50
°
C (14 to 122
°
F)
Allowable ambient humidity:
5 to 95
%
RH
(Absolute humidity: MAX.W.C 29.3 g/m
3
dry air at 101.3 kPa)
Installation environment conditions:
Indoor use
Altitude up to 2000 m