7. COMMUNICATION DATA MAP
32
IMR01Y35-E3
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
21
Logic output monitor
⎯
0044 68 RO
Bit
data
Bit 0: Logic output 1
Bit 1: Logic output 2
Bit 2: Logic output 3
Bit 3: Logic output 4
Bit 4: Logic output 5
Bit 5: Logic output 6
Bit 6: Logic output 7
Bit 7: Logic output 8
Bit 8 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 255]
⎯
22
Unused
⎯
0045
・
・
・
0060
69
・
・
・
96
⎯
⎯
⎯
23 PID/AT
transfer
CH1
CH2
CH3
CH4
0061
0062
0063
0064
97
98
99
100
R/W
0: PID
control
1: Autotuning
(AT)
0
24 Auto/Manual
transfer
CH1
CH2
CH3
CH4
0065
0066
0067
0068
101
102
103
104
R/W
0: Auto
mode
1: Manual
mode
0
25 Remote/Local
transfer
CH1
CH2
CH3
CH4
0069
006A
006B
006C
105
106
107
108
R/W 0: Local
mode
1: Remote
mode
When performing remote control by remote
setting input and also performing cascade control
and ratio setting, transfer to the Remote mode.
0
26 RUN/STOP
transfer
⎯
006D
109
R/W
0: STOP (Control stop)
1: RUN (Control start)
0
27
Memory area transfer
CH1
CH2
CH3
CH4
006E
006F
0070
0071
110
111
112
113
R/W
1 to 8
1
28 Interlock
release
CH1
CH2
CH3
CH4
0072
0073
0074
0075
114
115
116
117
R/W
0: Normal
state
1: Interlock release execution
0
29
Event 1 set value (EV1)
★
CH1
CH2
CH3
CH4
0076
0077
0078
0079
118
119
120
121
R/W
50
30
Event 2 set value (EV2)
★
CH1
CH2
CH3
CH4
007A
007B
007C
007D
122
123
124
125
R/W
50
31
Event 3 set value (EV3)
★
CH1
CH2
CH3
CH4
007E
007F
0080
0081
126
127
128
129
R/W
50
32
Event 4 set value (EV4)
★
CH1
CH2
CH3
CH4
0082
0083
0084
0085
130
131
132
133
R/W
Deviation action, Deviation action between
channels, Temperature rise completion range:
−
Input span to +Input span
Process action, SV action:
Input scale low to Input scale high
MV action:
−
5.0 to +105.0 %
If the Event type corresponds to “0: None,” set
to RO (Only reading data is possible).
When temperature rise completion is selected
at Event 3 action type.
If Event 4 corresponds to “9: Control loop
break alarm (LBA),” the Event 4 set value
becomes RO (Only reading data is possible).
50
33
Control loop break alarm
(LBA) time
★
CH1
CH2
CH3
CH4
0086
0087
0088
0089
134
135
136
137
R/W
0 to 7200 seconds (0: Unused)
480
34 LBA
deadband
★
CH1
CH2
CH3
CH4
008A
008B
008C
008D
138
139
140
141
R/W
0 (0.0) to Input span
0 (0.0)
★
:
Parameters which can be used in Multi-memory area function.
Continued on the next page.