7. COMMUNICATION DATA MAP
IMR01Y35-E3
37
Continued from the previous page.
Modbus
register address
No. Name Channel
HEX DEC
Attri-
bute
Data range
Factory
set value
81
Startup tuning (ST)
CH1
CH2
CH3
CH4
0146
0147
0148
0149
326
327
328
329
R/W
0: ST unused
1: Execute once *
2: Execute always
* When the Startup tuning (ST) is finished, the setting
will automatically returns to “0: ST unused.”
The Startup tuning (ST) function is activated
according to the ST start condition selected.
If control is Position proportioning control, set
to RO (Only reading data is possible).
0
82 Automatic
temperature
rise learning
CH1
CH2
CH3
CH4
014A
014B
014C
014D
330
331
332
333
R/W
0: Unused
1: Learning
*
* When the automatic temperature rise learning is
finished, the setting will automatically returns to
“0: Unused.”
If the Automatic temperature rise group
corresponds to "0: Automatic temperature rise
function OFF," set to RO (Only reading data is
possible).
0
83
Communication switch for
logic
⎯
014E 334
R/W
Bit
data
Bit 0: Communication switch 1
Bit 1: Communication switch 2
Bit 2: Communication switch 3
Bit 3: Communication switch 4
Bit 4 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 15]
0
84
Unused
⎯
014F
・
・
・
0175
335
・
・
・
373
⎯
⎯
⎯
Set data No. 85 or later are for Engineering setting [Writable in the STOP mode]
85 Input
type
CH1
CH2
CH3
CH4
0176
0177
0178
0179
374
375
376
377
R/W
0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PLII
12: RTD input Pt100
13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
22: Feedback resistance input 100 to 150
Ω
23: Feedback resistance input 151
Ω
to 6 k
Ω
If changed to Voltage (high) input from
TC/RTD/Current/Voltage (low)/Feedback
resistance input, select the hardware by the
input selector switch at the side of the module.
[Refer to
SRZ Instruction Manual (IMS01T04-E
)
]
Based on
model code
When not
specifying: 0
86 Display
unit
CH1
CH2
CH3
CH4
017A
017B
017C
017D
378
379
380
381
R/W
0:
°
C
1:
°
F
The engineering unit for Voltage/Current input
is expressed as %.
0
Continued on the next page.