116
IMR01Y35-E3
10. SPECIFICATIONS
PROFIBUS communication
Interface
:
Based on RS-485, EIA standard
Protocol:
PROFIBUS-DP
Communication speed:
9600 bps, 19200 bps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps,
12
Mbps
A master judges the quality situation of a line, and set it automatically.
Communications distance:
Refer to table shown below
Communication speed Maximum network length
12 Mbps
100 m
1.5 Mbps
200 m
500 kbps
400 m
187.5 kbps
1000 m
93.75 kbps
1200 m
19200 bps
1200 m
9600 bps
1200 m
Number of maximum connection nodes:
1 to 126
Number of stations:
32 stations (Can expand to 126 stations by use of the repeater)
Connection cable:
Special cable (Shielded twisted pair wire)
Connection method:
Connector
Termination resistor:
External installation is necessary
Data access types:
Static data read/write, Dynamic data read/write
Communication data length:
A maximum of 170 bytes can be read or written.
Controller communication
Interface:
Based on RS-485, EIA standard
Protocol:
Modbus-RTU
Synchronous method:
Start/stop synchronous type
Communication method:
2-wire system, half-duplex multi-drop connection
Communication speed:
9600 bps, 19200 bps, 38400 bps
Data bit configuration:
Data 8-bit, Without parity bit, Stop 1-bit
Number of maximum connections:
31 controllers (SRZ module) [Device address setting: 1 to 99]
Connection method:
Terminals
Termination resistor:
Built-in terminal base of COM-JG [ON/OFF select with switch (120
Ω
)]