Chapter 3: FRU Removal and Replacement Procedures
Additional Removal and Replacement Procedures
Quantum DXi6900-S Field Service Manual
175
Additional Removal and Replacement
Procedures
Some FRU procedures require removing and re-installing items in the Node that are not FRUs themselves.
Refer to the following procedures to remove and re-install non-FRU components in the Node:
l
Removing and Installing the Cooling Fan Assembly below
l
Removing and Installing the PCIe Card Holder on page 177
l
Removing and Installing the Cable Retention Bracket on page 178
l
Removing and Installing the Information Tag on page 180
Removing and Installing the Cooling Fan Assembly
To remove and replace the cooling fan assembly, refer to the following procedures:
l
Removing the Cooling Fan Assembly below
l
Replacing the Cooling Fan Assembly on the next page
Removing the Cooling Fan Assembly
To remove the cooling fan assembly:
1. Unlock the cooling fan assembly from the chassis by rotating the blue release lever upward (see
).
2. Lift the cooling fan assembly out of the chassis.
Figure 129:
Removing and Installing the Cooling Fan Assembly