Chapter 3: FRU Removal and Replacement Procedures
Hot-Swappable Parts
Quantum DXi6900-S Field Service Manual
61
Replacing Array or Expansion Module Hard Drives
Replacing Array or Expansion Module Power Supplies
Replacing an Array Module Controller
Replacing an Expansion Module ESM Canister
Replacing an Array or Expansion Module
Additional Removal and Replacement Procedures
Hot-Swappable Parts
Not all FRUs (Field Replaceable Units) and CRUs (Customer Replaceable Units) in the DXi6900-S are
capable of being removed and replaced during normal system operation (hot-swappable).
to determine if a part is hot-swappable, or if the system must be shut down to replace
the part (see ).
also indicates if use of the
Service Menu
is required to complete the FRU procedure (see
Accessing the DXi6900-S Service Menu on page 32
).
Table 1:
DXi6900-S Hot-Swappable FRUs and CRUs
Part
FRU
or
CRU
Hot-Swap
Capable
Shut
Down
Required
Service
Menu
Required
Node Parts
Solid State Drive
CRU
Yes
No
No
Power Supply
CRU
Yes
No
No
Cooling Fan
FRU
No
Yes
No
Memory Module
FRU
No
Yes
Yes
Dual SAS Card
FRU
No
Yes
Yes
Dual 10 GbE Card (Slots 4, 5, 7)
FRU
No
Yes
Yes