Chapter 3: FRU Removal and Replacement Procedures
Replacing Array or Expansion Module Power Supplies
Quantum DXi6900-S Field Service Manual
154
Obtaining a Replacement Array or Expansion Power
Supply
Before beginning the replacement procedure, make sure that you have the required replacement kit. The
appropriate replacement power supply will be provided by Quantum Customer Support (see
).
You will need the following items to perform this procedure:
l
Replacement power supply kit provided by Quantum Customer Support.
l
ESD grounding wrist strap (included in the replacement kit)
Figure 108:
DXi6900-S Array Module (RBOD) or Expansion Module (EBOD) Power Supply
Illustration
Description
Replacement power supply for DXi6900-S Array module
(RBOD) or Expansion module (EBOD)
(585 watt)
Replacing an Array or Expansion Power Supply
This section describes how to remove and replace a power supply in a DXi6900-S Array module (RBOD) or
Expansion module (EBOD). If a power supply fails, you will be notified by a service ticket in the remote
management console.
Caution:
Use appropriate ESD precautions, including the use of a grounding strap, when performing
this procedure.
Removing and replacing a power supply in an Array module (RBOD) or Expansion module (EBOD)
includes the following steps:
l
Identifying a Failed Power Supply in an Array or Expansion Module on the next page
l
Removing a Failed Power Supply from an Array or Expansion Module on page 156
l
Installing a Replacement Power Supply in an Array or Expansion Module on page 156