Chapter 3: FRU Removal and Replacement Procedures
Replacing Array or Expansion Module Hard Drives
Quantum DXi6900-S Field Service Manual
148
Figure 101:
Santricity Application
3. Click on the Qarray to view.
The Santricity Array Management appears (see
).
Figure 102:
Santricity Array Management
4. In the
Hardware
tab, Santricity displays the drives in the Array module (Tray 99) and any additional
Expansion modules (Tray 0) in the Qarray. A drive with an impending failure has a drive status of “Needs
Attention”.