717
Connections to Serial Communications Option Boards
Appendix F
NT-AL001 Link Adapter Settings
The NT-AL001 Link Adapter has a DIP switch for setting RS-422A/485 communications conditions. When con-
necting the Serial Communications Option Board, refer to the DIP switch settings shown in the following table.
Note
When connecting to a CP-series CPU Unit, turn OFF pin 5 and turn ON pin 6.
Connections for Host Link Communications
Port connections for Host Link communications are shown in the following table. Up to 32 nodes can be con-
nected for 1:N connections.
Note
(1) Four-wire connections must be used for RS-422A/485 connections with Host Link communications.
(2) “Resistance ON” indicates the terminating resistance must be turned ON.
(3) “5-V power” indicates that a 5-V power supply is required for the Link Adapter. Refer to the Link
Adapter manual for details. A 5-V power supply is not required for a Link Adapter connected to an
RS-232C Option Board mounted on the CPU Unit because power is supplied from pin 6 of the con-
nector.
(4) The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover
baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
Pin
Function
Factory setting
1
Not used. Always set this pin to ON.
ON
2
Built-in terminating resistance setting
ON: Connects terminating resistance.
OFF: Disconnects terminating resistance.
ON
3
2/4-wire setting
2-wire: Set both pins to ON.
4-wire: Set both pins to OFF.
OFF
4
OFF
5
Transmission mode (See note.)
Constant transmission: Set both pins to OFF.
Transmission performed when CTS signal in RS-232C interface is at high level:
Set pin 5 to OFF and pin 6 to ON.
Transmission performed when CTS signal in RS-232C interface is at low level:
Set pin 5 to ON and pin 6 to OFF.
ON
6
OFF
Port
Config-
uration
Schematic diagram, RS-232C ports
Schematic diagram, RS-422A/485 ports
Computer to
PLC: C-mode or
FINS com-
mands
PLC to com-
puter: FINS
commands
1:1
Computer to
PLC: C-mode or
FINS com-
mands
1:N
NT-AL001
RS-232C
RS-232C
RS-422A/485
5-V power
Resistance ON
NT-AL001
RS-232C
Resistance ON
Resistance ON
NT-AL001
RS-232C
RS-422A/485
5-V power
Resistance ON
(See note 1.)
Resistance ON
NT-AL001
RS-232C
RS-232C
RS-422A/485
5-V power
Resistance ON
NT-AL001
RS-232C
RS-232C
Resistance ON
NT-AL001
RS-232C
RS-422A/485
5-V power
Resistance ON
B500-AL001
RS-422A
/485
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...